Communication tab – Rockwell Automation 1756-XXXX ControlLogix Digital I/O Modules User Manual
Page 221

Rockwell Automation Publication 1756-UM058G-EN-P - November 2012
221
Use Ladder Logic To Perform Run Time Services and Reconfiguration
Appendix C
The following table lists tags used in the Source and Destination fields of the
message instructions.
If you are using RSLogix 5000 software, version 10.07.00 or later, choose the
physical location, slot number, and data type in the Source Element and
Destination fields.
Communication Tab
The Communication tab provides information on the path of the message
instruction. For example, the slot number of a 1756-OA8D module distinguishes
exactly which module a message is designated for.
Table 59 - Source and Destination Field Tags
Source Tag
Description
Enable_32_Points
DINT
Parameter used to determine which points are enabled for the service. That is, if
bit 0 = 1 for Reset Fuse, then point 0 has its electronic fuse reset.
Results_32_Points
DINT
Pass (0)/ Fail (1) result for the service. That is, if bit 0 = 1 for the results of the
Reset Fuse, then the Reset Fuse failed for point 0.
IMPORTANT
Use the Brown button to see a list of the I/O modules in the system. You choose
a path when you choose a module from the list.
You must name an I/O module during initial module configuration to choose a
path for your message instruction. Click OK to set the path.