Producer/Consumer Communication
By using Producer/Consumer communication, ControlLogix I/O modules can
produce data without first being polled by a controller. The modules produce the
data and any other owner-controller device can decide to consume it.
For example, an input module produces data and any number of processors can
consume the data at the same time. This eliminates the need for one processor to
send the data to another processor. For more information about this process, see
Input Module Operation on page 26
.
Status Indicator Information
Each ControlLogix digital I/O module has a status indicator on the front of the
module that lets you check the health and operational status of a module. The
status indicator displays vary for each module.
See
for examples of status indicators on ControlLogix digital I/O
modules.
Common Features
Specific to Input Modules
The table below lists features specific to ControlLogix digital input modules.
Status
Description
I/O status
ST
This yellow display indicates the On/Off state of the field device.
IMPORTANT: For the 1756-OA8D and 1756-OA8E modules, the I/O status indicator does not
illuminate without field power applied.
Module status
OK
This green display indicates the module’s communication status.
Fault status
FLT
This display is only found on some modules and indicates the presence or absence of various
faults.
Fuse status
Fuse
This display is only found on electronically fused modules and indicates the state of the
module’s fuse.