Rockwell Automation Publication 1783-IN001D-EN-P - January 2011

Wiring category

(1)

2 - on power ports
2 - on communication ports

North American temp code

T4

IEC temp code

T4

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1.

Environmental Specifications - Stratix 2000 Switches

Attribute

1783-US03T01F, 1783-US06T01F, 1783-US05T,
1783-US08T

Temperature, operating
IEC 60068-2-1 (Test Ad,

Operating Cold)

IEC 60068-2-2 (Test Bd,

Operating Dry Heat)

IEC 60068-2-14 (Test Nb,

Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, nonoperating
IEC 60068-2-1 (Test Ab,

Unpackaged Nonoperating
Cold)

IEC 60068-2-2 (Test Bb,

Unpackaged Nonoperating
Dry Heat)

IEC 60068-2-14 (Test Na,

Unpackaged Nonoperating
Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity
IEC 60068-2-30 (Test Db,

Unpackaged Damp Heat)

5…95% noncondensing

Vibration
IEC 60068-2-6 (Test Fc,

Operating)

2 g @ 10…500 Hz

Technical Specifications - Stratix 2000 Switches

Attribute

1783-US03T01F, 1783-US06T01F, 1783-US05T,
1783-US08T