Dataćtable interface area – Rockwell Automation 1771-TCM TEMPERATURE CONTROL User Manual
Page 11

1–4
Interfacing with the Temperature Control Module
Publication 1771Ć6.4.5 - January 1997
Download
Computer with
Temperature Control Software
DataĆTable Interface Area
PLC Data Table
RAM
Disk Files
Upload
For information on block-transfer programming, refer to your
Temperature Control Module User Manual (publication
1771-6.5.120)
To use the Temperature Control configuration software, the read and
write blocks, along with a control word, must be organized into a
614-word data-table interface area in an integer file with the word
offsets shown below. The utility ladder logic provides this.
Word Offset Description
0
Communication control word (initiates blockĆtransfer of configuration
autoĆtune, or gains values when you set a specific bit)
1
Used by the example ladder logic as: BT identity bits
2
Used by the example ladder logic as: BT check mask
3
Used by the example ladder logic as: Cycle sequence number
4
Used by the example ladder logic as: Loop offset value
5
Used by the example ladder logic as: DataĆtable file offset
6
Not used by the example ladder logic
7
Not used by the example ladder logic
8
Not used by the example ladder logic
9
Used by the example ladder logic as: TPO bits Ċ singleĆtransferred
10 - 39
LoopĆ1 configuration block (26 words)
40 - 69
LoopĆ2 configuration block (26 words)
70 - 99
LoopĆ3 configuration block (26 words)
100 - 129
LoopĆ4 configuration block (26 words)
130 - 159
LoopĆ5 configuration block (26 words)
160 - 189
LoopĆ6 configuration block (26 words)
190 - 219
LoopĆ7 configuration block (26 words)
220 - 249
LoopĆ8 configuration block (26 words)
250 - 309
Gains block (57 words)
310 - 349
Dynamic block (34 words)
350 - 419
Status block (64 words)
420 - 479
AutoĆtune block (system ID data) (57 words)
480 - 549
ScratchĆpad area addressed by the blockĆtransfer write instruction (64 words)
550 - 613
ScratchĆpad area addressed by the blockĆtransfer read instruction (64 words)
DataĆTable Interface Area