Error codes, Error codes -7 – Rockwell Automation 1762-IR4 RTD/Resistance Input Module User Manual
Page 75
Publication 1762-UM003A-EN-P - February 2003
Diagnostics and Troubleshooting 4-7
Error Codes
The table below explains the extended error code.
Table 4.3 Extended Error Codes
Error Type
Hex
Equivalent
(1)
Module
Error
Code
Extended Error
Information
Code
Error Description
Binary
Binary
No Error
X000
000
0 0000 0000
No Error
General Common
Hardware Error
X200
001
0 0000 0000
General hardware error; no additional information
X201
001
0 0000 0001
Power-up reset state
Module-Specific
Hardware Error
X300
001
1 0000 0000
General module hardware error
X301
001
1 0000 0001
Microprocessor hardware error
X302
001
1 0000 0010
A/D converter error
X303
001
1 0000 0011
Calibration error
Module-Specific
Configuration
Error
X400
010
0 0000 0000
General configuration error; no additional information
X401
010
0 0000 0001
Invalid input filter selected (channel 0)
X402
010
0 0000 0010
Invalid input filter selected (channel 1)
X403
010
0 0000 0011
Invalid input filter selected (channel 2)
X404
010
0 0000 0100
Invalid input filter selected (channel 3)
X405
010
0 0000 0101
Invalid input format selected (channel 0)
X406
010
0 0000 0110
Invalid input format selected (channel 1)
X407
010
0 0000 0111
Invalid input format selected (channel 2)
X408
010
0 0000 1000
Invalid input format selected (channel 3)
X409
010
0 0000 1001
Invalid excitation current for input range selected (channel 0)
X40A
010
0 0000 1010
Invalid excitation current for input range selected (channel 1)
X40B
010
0 0000 1011
Invalid excitation current for input range selected (channel 2)
X40C
010
0 0000 1100
Invalid excitation current for input range selected (channel 3)
X40D
010
0 0000 1101
Reserved bits set
(1) X represents the “Don’t Care” digit.