Rockwell Automation 1762-IR4 RTD/Resistance Input Module User Manual
Page 13
Publication 1762-UM003A-EN-P - February 2003
Overview 1-3
Table 1.1 RTD Specifications
RTD Type
(1)
Temperature Range Using
0.5 mA Excitation
Temperature Range Using
1.0 mA Excitation
Maximum
Scaled
Resolution
Maximum
Scaled
Repeatability
Copper 426
10
Ω
Not allowed
-100 to 260°C (-148 to 500°F)
0.1°C (0.1°F)
±0.2°C (±0.4°F)
Nickel 618
(2)
120
Ω
-100 to 260°C (-148 to 500°F)
-100 to 260°C (-148 to 500°F)
0.1°C (0.1°F)
±0.1°C (±0.2°F)
Nickel 672
120
Ω
-80 to 260°C (-112 to 500°F)
-80 to 260°C (-112 to 500°F)
0.1°C (0.1°F)
±0.1°C (±0.2°F)
Nickel-Iron
518
604
Ω
-100 to 200°C (-148 to 392°F)
-100 to +200°C (-148 to 392°F)
0.1°C (0.1°F)
±0.1°C (±0.2°F)
Platinum 385
100
Ω
-200 to 850°C (-328 to 1562°F)
-200 to 850°C (-328 to 1562°F)
0.1°C (0.1°F)
±0.2°C (±0.4°F)
200
Ω
-200 to 850°C (-328 to 1562°F)
-200 to 850°C (-328 to 1562°F)
0.1°C (0.1°F)
±0.2°C (±0.4°F)
500
Ω
-200 to 850°C (-328 to 1562°F)
-200 to 850°C (-328 to 1562°F)
0.1 °C (0.1 °F)
±0.2°C (±0.4°F)
1000
Ω
-200 to 850°C (-328 to 1562°F)
Not Allowed
0.1°C (0.1°F)
±0.2°C (±0.4°F)
Platinum 3916
100
Ω
-200C to 630°C (-328 to
1166°F)
-200 to 630°C (-328 to 1166°F)
0.1°C (0.1°F)
±0.2°C (±0.4°F)
200
Ω
-200 to 630°C (-328 to 1166°F)
-200 to 630°C (-328 to 1166°F)
0.1°C (0.1°F)
±0.2°C (±0.4°F)
500
Ω
-200 to 630°C (-328 to 1166°F)
-200 to 630°C (-328 to 1166°F)
0.1°C (0.1°F)
±0.2°C (±0.4°F)
1000
Ω
-200 to 630°C (-328 to 1166°F)
Not Allowed
0.1°C (0.1°F)
±0.2°C (±0.4°F)
(1) Digits following the RTD type represent the temperature coefficient of resistance (
α)
, which is defined as the resistance change per ohm per °C. For instance,
platinum 385 refers to a platinum RTD with
α
= 0.00385 ohm/ohm -°C, or simply 0.00385/°C.
(2) Actual value at 0°C is 100
Ω
per DIN standard.