Input data file, Input data values, General status flag bits (s0 to s3) – Rockwell Automation 1762-IR4 RTD/Resistance Input Module User Manual
Page 37

Publication 1762-UM003A-EN-P - February 2003
Module Data, Status, and Channel Configuration 3-3
Input Data File
The input data table allows you to access RTD input module read data
for use in the control program, via word and bit access. The data table
structure is shown in table below.
Input Data Values
Data words 0 through 3 correspond to channels 0 through 3 and
contain the converted analog input data from the input device.
General Status Flag Bits (S0 to S3)
Bits S0 through S3 of Word 3 contain the general status information for
channels 0 through 3, respectively. This bit is set (1) when an error
(over- or under-range, short-circuit, open-circuit, or input data not
valid) exists for that channel. The error conditions of the General
Status bits are logically ORed. Therefore, the user control program
determines which condition is setting the general status bit by viewing
the following bits: open-circuit, over-range, or under-range. The data
not valid condition is described on the following page.
Table 3.1 Input Data Table
Word/Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
RTD/Resistance Input Data Channel 0
1
RTD/Resistance Input Data Channel 1
2
RTD/Resistance Input Data Channel 2
3
RTD/Resistance Input Data Channel 3
4
Reserved
OC3
OC2
OC1
OC0
Reserved
S3
S2
S1
S0
5
U0
O0
U1
O1
U2
O2
U3
O3
Reserved
TIP
Status bits for a particular channel reflect the
configuration settings for that channel. To receive
valid status, the channel must be enabled and the
module must have stored a valid configuration word
for that channel.