3-6 Module Data, Status, and Channel Configuration

Configuration Data File

The configuration data file is shown below. Bit definitions are
provided in Channel Configuration on page 3-7. Detailed definitions
of each of the configuration parameters follows the table.

The default configuration of the table is all zeros, which yields the
following.

TIP

Normal channel configuration is done using
programming software. In that case, it is not
necessary to know the meaning of the bit
location. However, some systems allow
configuration to be changed by the control
program. Refer to your controller’s
documentation for details.

Table 3.2 Default Configuration

Parameter

Default Setting

Channel Enable/Disable

Disable

Data Format

Raw/Proportional

Input/Sensor Type

100

Platinum 385

Temperature Units/Mode

°C (not applicable with Raw/Proportional)

Open/Broken Circuit Response

Upscale

Cyclic Lead Compensation

Enable

Excitation Current

1.0 mA

Input FIlter Frequency

60 Hz