6 CompactBlock Distributed I/O on PROFIBUS DP Series D

Publication

1791P-IN002B-EN-P - October 2003

The switches are read at module power up only.

Mount the Block(s)

The base and expansion modules mount to a panel or DIN rail, which must
be grounded before installing the module(s).

Base Module Mounting

You can install the CompactBlock base module on a panel or DIN rail.

Address

DIP Switches

100’s

Rotary Switches

Position 1

Position 2

10’s

1’s

0-99

0

0

0-9

0-9

100-125

1

0

0-2

0-5

WARNING

When used in a Class I, Division 2, hazardous
location, this equipment must be mounted in a suitable
enclosure with proper wiring method that complies
with the governing electrical codes.

0

1

2

3

4

5

6

7

8

9

0

1

2

3

4

5

6

7

8

9

1

2

ON

10

’s

1’

s

Rotary Switches

(00-99)

Example: Node
Address is set at 26

43112

DIP Switches

(100-125)

View when looking into module.

100’s