beautypg.com

Rockwell Automation 1791P-XXXX CompactBlock Distributed I/O on PROFIBUS DP Series D I.I. User Manual

Page 27

background image

CompactBlock Distributed I/O on PROFIBUS DP Series D 27

Publication

1791P-IN002B-EN-P - October 2003

General Specifications (continued)

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0 to 60°C (32 to 140°F)

Field Wiring Tightening Torque

5-7lb-in. (0.5-0.6 Nm)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating

Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry

Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating

Thermal Shock):

–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):

5-95% non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

Operating 30g

Non-operating 50g

Vibration

IEC60068-2-6 (Test Fc, Operating):

5g @ 10-500Hz

Conductors Wire Size

Category

14 gauge (2mm

2

) stranded maximum

3/64 inch insulation maximum
2

2, 3

ESD Immunity

IEC 61000-4-2:

6kV contact discharge

8kV air discharge

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1kHz sine-wave 80%AM from 80MHz to

1000MHz

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

EFT/B Immunity

IEC 61000-4-4:

±2kV at 5kHz on signal ports

±2kV at 5kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:

±1kV line-line(DM) and ±2kV line-earth(CM) on signal

ports

±2kV line-earth(CM) on shielded

ports

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz to

80MHz

Emissions

CSPR 11:

Group 1, Class A