beautypg.com

North american hazardous location approval – Rockwell Automation 1791P-XXXX CompactBlock Distributed I/O on PROFIBUS DP Series D I.I. User Manual

Page 29

background image

CompactBlock Distributed I/O on PROFIBUS DP Series D 29

Publication

1791P-IN002B-EN-P - October 2003

North American Hazardous Location Approval

The following information applies when

operating this equipment in hazardous

locations:

Informations sur l’utilisation de cet équipement en

environnements dangereux :

Products marked “CL I, DIV 2, GP A, B, C, D”
are suitable for use in Class I Division 2 Groups
A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is
supplied with markings on the rating nameplate
indicating the hazardous location temperature
code. When combining products within a system,
the most adverse temperature code (lowest “T”
number) may be used to help determine the
overall temperature code of the system.
Combinations of equipment in your system are
subject to investigation by the local Authority
Having Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu’à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec des marquages
sur sa plaque d’identification qui indiquent le code de
température pour les environnements dangereux.
Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus défavorable
(code de température le plus faible) peut être utilisé pour
déterminer le code de température global du système.
Les combinaisons d’équipements dans le système sont
sujettes à inspection par les autorités locales qualifiées
au moment de l’installation.

The following information applies when

operating this equipment in hazardous

locations:

Informations sur l’utilisation de cet équipement en

environnements dangereux :

WARNING

EXPLOSION HAZARD

• Do not disconnect

equipment unless power
has been removed or the
area is known to be
nonhazardous.

• Do not disconnect

connections to this
equipment unless power
has been removed or the
area is known to be
nonhazardous. Secure any
external connections that
mate to this equipment by
using screws, sliding
latches, threaded
connectors, or other
means provided with this
product.

• Substitution of

components may impair
suitability for Class I,
Division 2.

• If this product contains

batteries, they must only
be changed in an area
known to be
nonhazardous.

AVERTISSEMENT

RISQUE D’EXPLOSION

• Couper le courant ou

s’assurer que
l’environnement est classé
non dangereux avant de
débrancher l'équipement.

• Couper le courant ou

s'assurer que
l’environnement est classé
non dangereux avant de
débrancher les
connecteurs. Fixer tous les
connecteurs externes reliés
à cet équipement à l'aide de
vis, loquets coulissants,
connecteurs filetés ou
autres moyens fournis avec
ce produit.

• La substitution de

composants peut rendre cet
équipement inadapté à une
utilisation en
environnement de Classe I,
Division 2.

• S’assurer que

l’environnement est classé
non dangereux avant de
changer les piles.