beautypg.com

Following are data tables on rslogix500, Maximum input data format (base modules -16b0), Maximum output data format (base modules -16b0) – Rockwell Automation 1791P-XXXX CompactBlock Distributed I/O on PROFIBUS DP Series D I.I. User Manual

Page 21: Maximum input data format (base modules -0b16p)

background image

CompactBlock Distributed I/O on PROFIBUS DP Series D 21

Publication

1791P-IN002B-EN-P - October 2003

Following are data tables on RSLogix500

.

Maximum Input Data Format (Base Modules -16B0)

Bit Position

Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

In15

In14

In13

In12

In11

In10

In9

In8

In7

In6

In5

In4

In3

In2

In1

In0

Base

1

Reserved

Analog Input Data Channel 0

2

Reserved

Analog Input Data Channel 1

3

Reserved

Analog Input Data Channel 2

4

Reserved

Analog Input Data Channel 3

5

URo1 URo0 ORo1 ORo0 OW3 OW2 OW1 OW0 ORi3 ORi2 ORi1 ORi0 Reserved

RF

UF

UF

Module Unrecoverable Fault

Set “0”: No Error

Set “1”: Error

RF

Module Recoverable Fault

Set “0”: No Error

Set “1”: Error

ORi x Over Range Input Channel

Set “0”: No Over Range

Set “1”: Over Range

OW x Input Open Wire (@ 4-20mA Range)

Set “0”: No Open Wire

Set “1”: Open Wire

ORo x Output Data Over Range

Set “0”: No Over Range

Set “1”: Over Range

URo x Output Data Under Range (@4-20MA Range)

Set “0”: No Under Range

Set “1”: Under Range

Bit 12-15 are not used to display correct data on the tool at decimal data type

Maximum Output Data Format (Base Modules -16B0)

Bit Position

Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Reserved

Analog Output Data Channel 0

1

Reserved

Analog Output Data Channel 1

Maximum Input Data Format (Base Modules -0B16P)

Bit Position

Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Reserved

Analog Input Data Channel 0

1

Reserved

Analog Input Data Channel 1

2

Reserved

Analog Input Data Channel 2

3

Reserved

Analog Input Data Channel 3

4

URo1 URo0 ORo1 ORo0

OW3

OW2

OW1 OW0 ORi3 ORi2 ORi1 ORi0

Reserved

RF

UF

UF

Module Unrecoverable Fault

Set “0”: No Error

Set “1”: Error

RF

Module Recoverable Fault

Set “0”: No Error

Set “1”: Error

ORi x Over Range Input Channel

Set “0”: No Over Range

Set “1”: Over Range

OW x Input Open Wire (@ 4-20mA Range)

Set “0”: No Open Wire

Set “1”: Open Wire

ORo x Output Data Over Range

Set “0”: No Over Range

Set “1”: Over Range

URo x Output Data Under Range (@4-20MA Range)

Set “0”: No Under Range

Set “1”: Under Range