Following are data tables on rslogix500, Maximum input data format (base modules -16b0), Maximum output data format (base modules -16b0) – Rockwell Automation 1791P-XXXX CompactBlock Distributed I/O on PROFIBUS DP Series D I.I. User Manual
Page 21: Maximum input data format (base modules -0b16p)
![background image](/manuals/579162/21/background.png)
CompactBlock Distributed I/O on PROFIBUS DP Series D 21
Publication
1791P-IN002B-EN-P - October 2003
Following are data tables on RSLogix500
.
Maximum Input Data Format (Base Modules -16B0)
Bit Position
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
In15
In14
In13
In12
In11
In10
In9
In8
In7
In6
In5
In4
In3
In2
In1
In0
Base
1
Reserved
Analog Input Data Channel 0
2
Reserved
Analog Input Data Channel 1
3
Reserved
Analog Input Data Channel 2
4
Reserved
Analog Input Data Channel 3
5
URo1 URo0 ORo1 ORo0 OW3 OW2 OW1 OW0 ORi3 ORi2 ORi1 ORi0 Reserved
RF
UF
UF
Module Unrecoverable Fault
Set “0”: No Error
Set “1”: Error
RF
Module Recoverable Fault
Set “0”: No Error
Set “1”: Error
ORi x Over Range Input Channel
Set “0”: No Over Range
Set “1”: Over Range
OW x Input Open Wire (@ 4-20mA Range)
Set “0”: No Open Wire
Set “1”: Open Wire
ORo x Output Data Over Range
Set “0”: No Over Range
Set “1”: Over Range
URo x Output Data Under Range (@4-20MA Range)
Set “0”: No Under Range
Set “1”: Under Range
Bit 12-15 are not used to display correct data on the tool at decimal data type
Maximum Output Data Format (Base Modules -16B0)
Bit Position
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Reserved
Analog Output Data Channel 0
1
Reserved
Analog Output Data Channel 1
Maximum Input Data Format (Base Modules -0B16P)
Bit Position
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Reserved
Analog Input Data Channel 0
1
Reserved
Analog Input Data Channel 1
2
Reserved
Analog Input Data Channel 2
3
Reserved
Analog Input Data Channel 3
4
URo1 URo0 ORo1 ORo0
OW3
OW2
OW1 OW0 ORi3 ORi2 ORi1 ORi0
Reserved
RF
UF
UF
Module Unrecoverable Fault
Set “0”: No Error
Set “1”: Error
RF
Module Recoverable Fault
Set “0”: No Error
Set “1”: Error
ORi x Over Range Input Channel
Set “0”: No Over Range
Set “1”: Over Range
OW x Input Open Wire (@ 4-20mA Range)
Set “0”: No Open Wire
Set “1”: Open Wire
ORo x Output Data Over Range
Set “0”: No Over Range
Set “1”: Over Range
URo x Output Data Under Range (@4-20MA Range)
Set “0”: No Under Range
Set “1”: Under Range