Commands: write-only – Rockwell Automation 1420 PowerMonitor 500 User Manual
Page 59
![background image](/manuals/579039/59/background.png)
Rockwell Automation Publication 1420-UM001D-EN-P - September 2013
59
PowerMonitor 500 Unit Data Tables
Appendix A
Table 30 - Commands: Write-only
Modbus
Address
Length
(words)
Description / Units
Data Format
Notes
312369
1
Get clock values
UINT
Value=1 - command executed; Value
1 - no effect
312370
1
Set clock values
UINT
Value=1 - date and time set
312374
1
Enable optional pulse (digital) outputs
UINT
Value=1 - module enabled; Value=0 - module disabled
312376
1
Enable optional serial communication
UINT
Value=1 - module enabled; Value=0 - module disabled
312546
1
Reset all pulse (digital) outputs (digital
output 1 or 2)
UINT
Value=1 - command executed; Value
1 - no effect
312547
1
Set pulse (digital) output 1
UINT
Value=0 - reset output; Value=1 - set output; Other values - no
effect
312548
1
Set pulse (digital) output 2
UINT
Value=0 - reset output; Value=1 - set output; Other values - no
effect
312549
1
Set all pulse (digital) outputs (digital
output 1 or 2)
UINT
Value=1 - command executed; Value
1 - no effect
312802
1
Reset V L1-N
UINT 16
Bit0 = 1: Reset Max Value
Bit1 = 1: Reset DMD value
Bits 2 … 15: Reserved
312803
1
Reset V L2-N
UINT 16
312804
1
Reset V L3-N
UINT 16
312805
1 Reset
V
L-N
UINT
16
312806
1
Reset V L1-L2
UINT 16
312807
1
Reset V L2-L3
UINT 16
312808
1
Reset V L3-L1
UINT 16
312809
1 Reset
V
L-L
UINT
16
312810
1
Reset A L1
UINT 16
312811
1
Reset A L2
UINT 16
312812
1
Reset A L3
UINT 16
312813
1
Reset A N
UINT 16