beautypg.com

Rockwell Automation 1420 PowerMonitor 500 User Manual

Page 24

background image

24

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013

Chapter 3

Unit Configuration

Table 4 - Front Panel Display Descriptions

Display Item Description

Navigating Menus

Editing a Menu

1

Programming mode indicator

Indicates programming mode.

2

Programming menu page

Identifies the current programming menu page. Refer to the programming flow chart beginning on

page 26

.

3

Editing mode indicator

Does not appear.

Indicates the parameter being edited.

4

Cursor

Does not appear.

Appears beneath the digit currently being edited.

5

Permitted range

Displays the permitted range of values for the selected parameter.

6

Exit button

When in a menu page, exits Programming mode.

Program/select button confirms exit.

When in a sub-menu page, exits to menu page.

Moves the cursor one digit to the left.

When the leftmost digit is selected, dP is

indicated and you can change the decimal point
and multiplier (see

Editing Decimal Point and

Multiplier on page 25

).

When held for at least 2 seconds, cancels the edit

and restores the previous value of the selected
parameter.

7

Up button

Selects the next higher-numbered menu or sub-
menu page.

Increments the value of the digit indicated by the

cursor.

When dP is indicated, increments the decimal

point and multiplier .

Down button

Selects the next lower-numbered menu of sub-
menu page.

Decrements the value of the digit indicated by

the cursor.

When dP is indicated, decrements the decimal

point and multiplier .

8 Program/select

button

Selects a menu page for editing.

When in a menu page with sub-menus, displays

the first sub-menu page.

After pressing the Exit button, confirms exit from

Programming mode.

From End menu page 260, saves new

configuration and exits Programming mode.

Stores the new value of the selected parameter, but
does not save the new configuration to the power
monitor.

IMPORTANT

To save programming changes, navigate to the End menu page 260 and press
Program/select. To exit the Programming mode without saving any changes,
press Exit and confirm by pressing Program/select. If no buttons have been
pressed for two minutes, the power monitor exits Programming mode without
saving any changes.