Rockwell Automation 1420 PowerMonitor 500 User Manual
Page 24
24
Rockwell Automation Publication 1420-UM001D-EN-P - September 2013
Chapter 3
Unit Configuration
Table 4 - Front Panel Display Descriptions
Display Item Description
Navigating Menus
Editing a Menu
1
Programming mode indicator
Indicates programming mode.
2
Programming menu page
Identifies the current programming menu page. Refer to the programming flow chart beginning on
.
3
Editing mode indicator
Does not appear.
Indicates the parameter being edited.
4
Cursor
Does not appear.
Appears beneath the digit currently being edited.
5
Permitted range
Displays the permitted range of values for the selected parameter.
6
Exit button
• When in a menu page, exits Programming mode.
Program/select button confirms exit.
• When in a sub-menu page, exits to menu page.
• Moves the cursor one digit to the left.
• When the leftmost digit is selected, dP is
indicated and you can change the decimal point
and multiplier (see
• When held for at least 2 seconds, cancels the edit
and restores the previous value of the selected
parameter.
7
Up button
Selects the next higher-numbered menu or sub-
menu page.
• Increments the value of the digit indicated by the
cursor.
• When dP is indicated, increments the decimal
point and multiplier .
Down button
Selects the next lower-numbered menu of sub-
menu page.
• Decrements the value of the digit indicated by
the cursor.
• When dP is indicated, decrements the decimal
point and multiplier .
8 Program/select
button
• Selects a menu page for editing.
• When in a menu page with sub-menus, displays
the first sub-menu page.
• After pressing the Exit button, confirms exit from
Programming mode.
• From End menu page 260, saves new
configuration and exits Programming mode.
Stores the new value of the selected parameter, but
does not save the new configuration to the power
monitor.
IMPORTANT
To save programming changes, navigate to the End menu page 260 and press
Program/select. To exit the Programming mode without saving any changes,
press Exit and confirm by pressing Program/select. If no buttons have been
pressed for two minutes, the power monitor exits Programming mode without
saving any changes.