beautypg.com

Rockwell Automation 1420 PowerMonitor 500 User Manual

Page 37

background image

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013

37

Communication

Chapter 4

We assume that you are familiar with basic message programming in a Logix

controller. Once you have set up the logic, message tag, destination tag, and

message instruction, follow these steps to configure the message. This example

uses a CompactLogix controller, revision 20.

1. Choose the appropriate parameters in the Message Configuration window.

Parameter

Choice

Message Type

Choose message type CIP Generic.

Service Type

Read: Select service type Get Attribute Single (E hex)

Instance Refer

to

Appendix A

for the CIP Instance of the data table to read. In this example, the power

monitor's Real-time Metering Values (Voltage and Current) data table is instance 101 (decimal).

Class 4

hex

Attribute 3

hex

Destination

Get Attribute Single - This is the first element of the controller tag that stores the data being
read. The tag is an array of the applicable data type the same length as the assembly instance; in
this example, 12 REAL elements.

Source Element

Not applicable to a Read

Source Length

Not applicable to a Read