Rockwell Automation 1420 PowerMonitor 500 User Manual
Page 39
Rockwell Automation Publication 1420-UM001D-EN-P - September 2013
39
Communication
Chapter 4
4. Enter the setup parameters as listed in this dialog box and explained in
.
Table 5 - Module Properties Setup Parameters
Item
Choices
General Tab
Name
Required; must be IEC 1131-3 compliant
Description
Optional
Comm Format
Depends on selected Assembly Instance
(1)
Address/Host Name
IP Address
IP address of target PowerMonitor 500 unit
Host Name
Not applicable
Connection Parameters
Assembly Instance
Size
Comm Format
Data Table Description
Input (select one)
100
20
Input Data - SINT
Product Information
101
12
Input Data - REAL
Real-time Voltage and Current
102
18
Input Data - REAL
Real-time Power, PF, Frequency
103
12
Input Data - REAL
MAX Voltage and Current
104
17
Input Data - REAL
MAX Power, PF, Frequency
105
12
Input Data - REAL
Dmd Voltage and Current
106
17
Input Data - REAL
Dmd Power, PF, Frequency
107
18
Input Data - REAL
Energy Meters
108
2
Input Data - INT
Alarm and Output Status
Output
98
N/A
Inst. 98 used for Input Only connection
99
N/A
Inst. 99 used for Listen Only connection1
Configuration
3
0
Instance 3 is a placeholder only
Connection Tab
RPI
100 ms or greater
Inhibit Module
Optional - unchecked by default
Major Fault
Optional - unchecked by default
Unicast Connection
Optional - checked by default
(1) Use the Listen Only connection only when an Input Only connection exists with another controller.