1336 FORCE-5.19 – August, 2000
Introduction
1-7
In parameter 81 (Non-Configurable Fault Status), bit 5 Master/ Slave
Cable Loss and bit 6 Master Slave Enable Timeout are specific to the
Master/Slave drives. Faults specific to the Master/Slave drives and
their probable causes are covered in greater depth in Chapter 4,
Troubleshooting.
Specifications
Specifications for the Master/Slave version of the 1336 FORCE drive
match those of standalone units in the the areas of:
•
Control Specs (see publication1336 FORCE 5.12)
•
Options (see publication 1336 FORCE 5.12)
•
Standard Features (see publication 1336 FORCE 5.12)
•
Options (see publication 1336 FORCE 5.12)
•
Protective Features (see publication 1336 FORCE 5.12)
•
Environmental Specifications (see publication 1336 FORCE
5.12)
•
Feedback Devices (see publication 1336 FORCE 5.12)
Areas where the Master/Slave version differs from the standard
FORCE drive include:
Electrical Specifications -
•
Input Voltage Rating: 380 - 575V (G & H Frame Drives), 3
Phase, +10%, -15% nominal
•
Input Power Rating: 4-1110 KVA (460V)
4-1156 KVA (500V)
6-1388 KVA (600V)
•
Input Frequency: 50/60Hz (+/- 3Hz)
•
Standard Output Voltage: Each frame size is line dependent and
can power a motor between the following voltages:
G Frame -380 - 480 VAC (line dependent)
500 - 600 VAC (line dependent)
H Frame - 500 - 600 VAC (line dependent)
•
Output Current: 5-1346A
•
Output Power: 4 - 380 KVA (380 V)
4 - 416 KVA (415V)
4 - 1074 KVA (460V)
4 - 1342 KVA (575V)
•
Output Horse Power (Continuous): 1000 - 1600 HP
•
Overload Capability: 100% Fundamental current (each
standalone inverter)
1 minute - 150% (each standalone inverter)
For example: While the overload capability of the M/S drive does
not exceed 150%, it could be viewed as having a 1 minute
overload capability, as each drive is capable of 150% for 1 min.