If an operating problem occurs, use the following troubleshooting chart to

isolate the cause of the failure and find the corrective action. If the corrective

action fails to resolve the problem, consult your local Rockwell Automation field

support representative.

1502-UM051E-EN-P – June 2013

Table 5.A – Troubleshooting (Series D contactors)

Symptom

Possible Cause

Remedy

Contactor

chatters

• Loose connections in control circuit

• Improper control wiring

• Control voltage

• Mechanical latch not engaging

• Improper set-up of auxiliary contact

assembly

• Faulty auxiliary contacts

• Faulty CR1 or CR2 interposing relay

• Check all connections in control circuit for tightness.

Check wiring from the coil to the terminal block assembly.

• Check wiring per schematic.

• Measure control voltage. Refer to Contactor Specifications

for minimum pick-up voltage.

• Check for free movement of latch lever.

• Check set-up of auxiliary contact assembly.

• Check master contact cartridges on contactor.

• Check CR1 and CR2 relay.

Coil burnout

• Coil leads improperly wired

• Control voltage too high

• Contactor operated too frequently

• Check wiring from the coil to the terminal block assembly.

• Check for correct control voltage

• Check switching frequency:

– 600 ops/hr electrically held

– 150 ops/hr mechanically held

Contactor

does not

energize

• Loose connections in control circuit

• Improper control wiring

• Control voltage

• Improper set-up of auxiliary contact

assembly

• Faulty CR1 or CR2 interposing relay

• Check all connections in control circuit for tightness.

Check wiring from the coil to the terminal block assembly.

• Check wiring per schematic.

• Measure control voltage. Refer to Contactor Specifications

for pick-up voltage.

• Check set-up of auxiliary contact assembly.

• Check CR1 and CR2 relay.

For Series E contactors with IntelliVAC control or IntelliVAC Plus control, refer to Publications 1503-UM053_-EN-P or 1503-UM054_-EN-P

respectively.