Contactor specifications – Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual
Page 11
Contactor Product Description
1-7
1502-UM051E-EN-P – June 2013
Contactor
Specifications
Table 1.B - Bulletin 1502 Medium Voltage 800 Amp Contactor Ratings
Description
Specifications
Voltage Ratings
Maximum Rated Voltage
7200
System Voltages
2400
3300
4160
4800
6600
6900
Dielectric Voltage Withstand Rating
For 60 seconds (kV)
18.2 / 20 (IEC)
Basic Impulse Level (B.I.L.) Withstand
Phase to Ground, Phase to Phase (kV)
60
Frequency Ratings
Hertz
50 / 60
Current Ratings
Rated Continuous Current (Amps)
800
2400 V (RMS Sym Amps)
12,500
5000 V (RMS Sym Amps)
12,500
Maximum Interrupting Current Rating
7200 V (RMS Sym Amps)
12,500
2400 V (Sym MVA)
50
5000 V (Sym MVA)
100
Maximum Interrupting MVA Rating
7200 V (Sym MVA)
150
Short-Circuit Withstand at Rated Voltage Current Peak ½ cycle (kA)
85
For 1 second (kA)
12.0
Short Time Current Rating Capability
For 30 seconds (kA)
4.8
Chop Current (Average RMS Amps)
0.5
Make and Break Capability at Rated Voltage (kA)
8.0
Ambient Temperature
°C
40
Contactor Coil Data (Series E)
Control Voltage
(V
CTL
)
Coil Voltage (V
CL
)
Close Current (A
DC
, 200 milliseconds)
12
Hold Current (A
DC
)
0.7
Pick-up Voltage
95
Drop-out Voltage
75
Trip Current (A
DC
, 200 milliseconds)
5.2
110 to 240 VAC
or
110 to 250 VDC
VAC:
V
CL
=
X V
CTL
(Max.)
VDC:
V
CL
= V
CTL
Trip Voltage
70
Close Current (A
DC
)
13.1
Hold Current (A
DC
)
0.24
Trip Current (A
DC
)
5.6
Pick-up Voltage
102
120 VAC
110 VDC
Trip Voltage
84
Contactor Coil Data (Series D)
Control Voltage
(V
CTL
)
Coil Voltage (V
CL
)
Coil Inrush Current (A) – Electrically Held
13.1 / 7.1
Coil Inrush Current (A) – Mechanical Latch
13.1 / NA
Coil Inrush Current (A) – Mechanical Latch Trip
5.6 / NA
Coil Continuous Current (A)
0.24 / 0.13
Coil Pick-up Voltage (VAC)
102 / 196
120 VAC/
230 VAC
110 VDC/
208 VDC
Coil Drop-out Voltage (VAC)
75 / 145
The voltage and current ratings listed are valid up to 1,000 m (3,300 feet). Please refer to Table 1.C – Altitude Derating Chart, on page
1-8 for ratings above this altitude.
Control voltage, as measured at the input of the IntelliVAC or IntelliVAC Plus control module.
Provided that regular maintenance is performed.
A contactor drop-out delay may be configured with the IntelliVAC control module (refer to publication 1503-UM053_-EN-P), or the
IntelliVAC Plus control module (publication 1503-UM054_-EN-P).
FDO = Fast Drop-Out. NDO = Normal Drop-Out.
The number of contactor auxiliary contacts depends on the contactor type. Some of the contacts are used in the typical control
schemes used.
2