1502-um051_chapter 3_june2013, Installation, Chapter – Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual
Page 18: Mounting, Figure 3.1 – contactor mounting details
Installation
Mounting
The Allen-Bradley vacuum contactor is normally fixed mounted (bolted down) in
the enclosure of the controller. There are four (4) mounting holes at the base of
the contactor (Figure 3.1) to secure it to the enclosure. For reversing, autotrans-
former and 2-speed controllers, one contactor may be mounted on top of the
other. There are four (4) threaded mounting holes at the top of the contactor to
accommodate this configuration.
IMPORTANT: The contactor is a bolted assembly and is therefore subject to twisting if fastened to an uneven surface.
The contactor mounting plate has small stand-offs that permit the contactor to be fastened without twisting the frame.
The contactor may not function correctly if it is forced onto an uneven mounting surface.
97,2 [3.83]
13,49 [0.531]
19,1 [0.75]
38,1 [1.50] (Typical Terminal Detail)
19,1 [0.75]
31,8 [1.25]
152,4 [6.00]
(Mounting Hole Centers)
12,7 [0.50]
41,3 [1.63]
127
[5.00]
462,5
[18.21]
437,1 [17.21]
457.2 [18.00] (Mounting Hole Centers)
127
[5.00]
104,2
[4.10]
32,4
[1.27]
14.27 [0.562]
(4) Mounting Holes
17,5 [0.69]
194,1 [7.64]
260,7 [10.27]
324,2 [12.77]
270 [10.63]
194,1 [7.64]
158,2�
[6.23]
267,31�
[10.52]
438,7�
[17.27]
16,7
[0.66]
Dimensions = mm [inches]
Figure 3.1 – Contactor Mounting Details
Chapter
3
1502-UM051E-EN-P – June 2013