beautypg.com

Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual

Page 42

background image

Maintenance

4-13

1502-UM051E-EN-P – June 2013

Referring to Figure 4.18 for Series D or Figure 4.19 for Series E mechanical-

ly latched contactors, connect the leads from the coil to the terminal block

assembly as follows:

Series D:

• Closing coil (yellow lead) to "H1"

• Closing coil (black lead) to "H2"

• Hold-in coil (yellow lead) to "C1"

• Hold-in coil (blue lead) to "C2"

• Trip Coil (white lead) to "D"

• Trip Coil (blue lead) to "B"

Series E:

• Closing coil (yellow lead) to "C"

• Closing coil (black lead) to "A"

• Trip Coil (white lead) to "D"

• Trip Coil (blue lead) to "B"

Note: The contactor will have either a high density (1492-HC6) or a regular

(1492-HJ86) terminal block. The wiring convention is the same for both types.

Hold -in coil (blue lead)

MOVs

Hold -in coil (yellow lead)

Closing coil (black lead)

Closing coil (yellow lead)

Figure 4.15 – Terminal Block Assembly (Electrically held Series D Contactor,

regular terminal block)

Hold -in coil (blue lead)

MOVs

Hold -in coil (yellow lead)

Closing coil (black lead)

Closing coil (yellow lead)

Figure 4.16 – Terminal Block Assembly (Electrically Held Series D Contactor,

high density terminal block)

Note: Figures 4.15 and 4.16 show the fast drop-out
configuration. The normal drop-out contactor has only
one (1) MOV.