Vacuum bottle integrity test (cont.) – Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual
Page 16

2-4
Receiving and Handling
1502-UM051E-EN-P – June 2013
High-voltage is present during this test. Caution should
be exercised during this test since high
voltage testing is
potentially hazardous.
Before doing any work on the contactor, the controller isolat-
ing switch must be in the open position and locked out. If
any control power is used from a separate source, it should
also be isolated. It is also suggested that a “Hot Stick” be
used to ensure equipment is voltage free.
1. The contactor may be tested while it is in the power cell. The line connec-
tion of the contactor must be disconnected and the ground lead from the
Hi-pot tester must be connected to the load side of the contactor.
2. With the contactor in the open position, connect the test leads to the
contactor power terminals as shown in Figure 2.2. It is recommended that
an AC hi-pot tester be used. Apply 16 kV for 60 seconds and monitor the
leakage current. It should not exceed 5 mA.
3. If no breakdown occurs, the bottle is in an acceptable condition. If a break-
down occurs, the bottle should be replaced.
Note: Rockwell Automation recommends that, if the contactor has been in
service, all three (3) bottles be replaced at the same time.
4. After the HIGH POTENTIAL VOLTAGE is removed from the bottles,
the metal end caps of the bottles should be discharged with a grounding rod
to remove any residual electrical charge.
Figure 2.2 – Vacuum Bottle Integrity Test Circuit
Vacuum Bottle Integrity Test
(cont.)
A T T E N T I O N
A T T E N T I O N
S H O C K H A Z A R D