beautypg.com

Oem starter frame installation, Chapter – Rockwell Automation 1503 OEM Starter Frame Components Installation Manual User Manual

Page 5

background image

Chapter

1

OEM Starter Frame Installation

Read this document before performing any installation

procedures or adjustments. Observe all applicable

safety procedures when working on the equipment.

Complete all installation procedures before connecting

the incoming line cable. Failure to do so may result in

damage to the equipment or injury to personnel.

Receiving

Refer to General Handling Procedures for Medium Voltage Controllers

– Publication MV-QS050_-EN-P. This document is included with your

shipment and contains information regarding receiving, unpacking, initial

inspection, handling, storage, opening the medium voltage doors, and site

preparation.

Note: Refer to Appendix A for a listing of the items that are included in

your OEM Frame Kit.

Installation

Standards and Codes

The OEM starter frame consists of a fusible non-load-break

isolation switch, an isolation switch handle, a vacuum contactor, control

circuitry and a medium voltage door. These components are not a complete

motor controller. The user must add appropriate control circuitry for the

application, power fusing, current transformer, control power transformer,

overload protection and a suitable enclosure. It is recommended that the

user be familiar with the following safety and design standards and codes,

and any additional local codes that a medium voltage starter must comply with.

• CEC (Canadian Electrical Code)

• CSA 22.2 No. 14 (Canadian Standards Association) – Industrial Control

Equipment

• NEC (National Electrical Code)

• NEMA ICS Standards (National Electrical Manufacutrers’ Association)

• OSHA (Occupational Safety and Health Administration)

• UL 50 (Underwriters Laboratories) – Enclosures for Electrical Equipment

• UL 347 (Underwriters Laboratories) – High voltage Industrial Control

Equipment

• UL 508 (Underwriters Laboratories) – Industrial Control Equipment

• IEC 60204-1 – Safety of Machinery – Electrical Equipment of Machines,

Part 1: General Requirements

• IEC 62271-200 – AC Metal Enclosed Switchgear and Control Gear for

Rated Voltages Above 1kV and up to 52 kV

• IEC 60470 – High Voltage Alternating Current Contactors

• IEC 60529 – Degrees of Protection Provided by Enclosures (IP Code)

• IEC 62271-1 – Common Clauses for High voltage Switchgear and

Control Gear Standards

1503-IN050E-EN-P – June 2013

A T T E N T I O N

A T T E N T I O N

I M P O R T A N T

I M P O R T A N T