Specifications – Rockwell Automation MV SMC Flex OEM Components User Manual
Page 10
3-2
Power Stack Frame Installation
1503E-IN001E-EN-P – June 2013
Description of Frame Options
Catalog Number
Part Number
1000V, 180 A, 3 phase, 50/60 Hz
1503E-FRZ1T
80187-547-51
1000V, 360 A, 3 phase, 50/60 Hz
1503E-FRZ1A
80187-547-52
2300V, 180 A, 3 phase, 50/60 Hz
1503E-FRAT
80187-547-53
2300V, 360 A, 3 phase, 50/60 Hz
1503E-FRAA
80187-547-54
3300V, 180 A, 3 phase, 50/60 Hz
1503E-FRCT
80187-547-55
3300V, 360 A, 3 phase, 50/60 Hz
1503E-FRCA
80187-547-56
4160V, 180 A, 3 phase, 50/60 Hz
1503E-FRET
80187-547-57
4160V, 360 A, 3 phase, 50/60 Hz
1503E-FREA
80187-547-58
Voltage ranges :
1000 = 800 to 1449 V
2300 = 1450 to 2499 V
3300/4160 = 2500 to 4799 V
Table 3.B – Power Stack Frame Specifications
Description
180 A
360 A
Input Voltages
(50/60 Hz)
1000 volts AC, 3 phase, +10% -15%
2300 volts AC, 3 phase, +10% -15%
3300 volts AC, 3 phase, +10% -15%
4160 volts AC, 3 phase, +10% -15%
Ambient Temperature
0°C to 40°C (32°F to 104°F)
Power Section
6 SCR at 1000 volts
12 SCR at 3300 volts
6 SCR at 2400 volts
12 SCR at 4160 volts
Repetitive Peak
Inverse Voltage Rating
1000 volts – 4500 PIV
3300 volts – 13000 PIV
2300 volts – 6500 PIV
4160 volts – 13000 PIV
Thermal Capacity
600% of FLA, 10 seconds (2 starts per hour, 5 minutes between starts)
450% of FLA, 30 seconds (2 starts per hour, 5 minutes between starts)
dv/dt Protection
R.C. Snubber Network
Maximum Heat
Dissipation (kW)
Start or Stop Cycle (@ 450% FLA)
Continuous
180 A
360 A
800 to 2499 V
7
13
.25
2500 to 4799 V
14
26
.25
Altitude
0 to 1000 m (0 to 3,300 ft)
(See Controller Deratings Table A-1 in Appendix A)
Net Weight
(Shipping)
1000 to 2300 V – 116 kg (255 lbs)
3300 to 4160 V – 125 kg (276 lbs)
Refer to Table 3.A for acceptable input voltage ranges.
For higher ambient conditions, contact Factory.
Specifications