beautypg.com

Scale factor conversion – Rockwell Automation 193 193-5.0: Bulletin 913/592 SMP-3 Solid-State Overload Relay User Manual

Page 75

background image

Chapter 6 – Serial Communication

6-5

Scale Factor Conversion

When reading the average current parameter data in the logic
controller’s input table, divide these values by the scaling
values shown in Table 6.D to determine the “display units.”

Table 6.D Average Current and FLC Setting Scaling

Current Range

(FLC Range)

Scaling Factor

0.7–2.5 A

100x value

2–10 A

10x value

8–37 A

10x value

20–75 A

1x value

20–90 A

1x value

40–180 A

1x value

70–304 A

1x value

100–414 A

1x value

140–608 A

1x value

The value received will be scaled by the number shown. To recover the actual
value, divide the received value by the scaling factor shown.