Logic control data – Rockwell Automation 193 193-5.0: Bulletin 913/592 SMP-3 Solid-State Overload Relay User Manual

Page 72

background image

Chapter 6 – Serial Communication

6-2

Logic Control Data

The information in Table 6.B illustrates the logic control data that is sent to the SMP-3 overload relay through the logic controller
output image table. When using the Bulletin 1203-GD1 communication module, this information is sent to the SMP-3 overload
relay when SW3 dip 2 on the 1203-GD1 module is ON.

Table 6.B SMP-3 Logic Control Data

Bit

tat

ett

xp a at

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Status

Setting

Explanation

X

Turn Out A off

1

Turn Out A off

X

Turn Out B off

1

Turn Out B off

X

Clear Fault

1

Clear Fault

X

Turn Out A on

1

Turn Out A on

X

Turn Out B on

1

Turn Out B on

X

X

X

X

X

X

X

X

Not Used

X

XXX

X

X

X

Analog Parameter Selection

001
010
011
100

Average Current
Thermal Capacity Utilized
Full Load Current Setting
Current Unbalance

These three bits are used to specify/request the analog reference parameter the
SMP-3 overload relay should send back with the SMP-3 Status Data.

Note: The Turn Triac Off, Turn Triac On, and Clear Fault
signals are edge sensitive.