Table A.1 Specifications
ELECTRICAL – CONTROL CIRCUIT
Power Supply Input
Voltage Rating
110/240 VAC, 50/60 Hz
Operating Range
85 to 264 VAC, 47–63 Hz
Maximum Power Consumption
6 watts
Maximum Power Interruption Time
20 ms.
Trip Relay Output
For all except
193- or 592-CIL_
or CIM_
For 193- or
592-CIL_ or CIM_
Type
Hard Contact
Rated Operational Voltage
240 VAC
Contact Rating Designation
B300
A300
Maximum Operating Current
5 mA
10 mA
Minimum Operating Current
10 mA
100 mA
Minimum Leakage Current ➀
10 mA
10 mA
Resistive Load Rating (pF = 1.0)
5A, 250 VAC
5A, 30 VDC
10A, 250 VAC
10A, 30 VDC
Inductive Load Rating
(pF = 0.4)
(L/R = 7ms)
2A, 250 VAC
2A, 30 VDC
3A, 250 VAC
3A, 30 VDC
Recommended Control Circuit Fuse
6A Form 101
Semi-conductor
Fuse
(Gould P/N
A60 Q6-2)
12A Form 101
Semi-conductor
Fuse
(Gould P/N
A60 Q12-2)
Rated Number of Operations
10,000
OUT A and OUT B Outputs
For all except
193- or 592-CIL_
or CIM_
For 193- or
592-CIL_ or CIM_
Type
Triac
Rated Insulation Voltage
250 VAC
Operating Range
85 to 264 VAC, 47–63 Hz
Switching Element Rating
Designation
SE
SD
Utilization Category
AC15
AC15
Rated Operational Current
0.5A
1.0A
Minimum Operational Current
20 mA
50 mA
Maximum Off-state Current
10 mA
10 mA
Maximum Voltage Drop
3.5V
3.5V
Replaceable Fuse
(Ceramic 5
20mm, 250 VAC
2.0A
5.0A
Recommended Control Circuit Fuse
1A Class CC
(ATQR-1)
5A Form 101 Semi-
conductor Fuse
(Gould P/N
A60 Q5-2)
Maximum Bul. 500 Contactor Coil
Size 2
110–240 VAC
Size 4
110–240 VAC
Maximum Bul. 100 Contactor Coil
A75
110–240 VAC
B180
110–240 VAC
Rated Number of Operations
10,000,000
➀
Leakage current is due to noise suppression circuitry.