Appendix a – Rockwell Automation 193 193-5.0: Bulletin 913/592 SMP-3 Solid-State Overload Relay User Manual
Page 102

Appendix A –
Specifications
A-2
ELECTRICAL – CONTROL CIRCUIT (cont.)
Motor Current
Phases
Three-phase or SIngle Phase
Rated Insulation Voltage
660 VAC
Maximum Operational Current
(See Cat. No. Code Explanation)
Operational Frequency
50–60 Hz
Current Wave Shape
Undistorted Sinusodial
ENVIRONMENTAL
Ambient Temperature
Storage
–40
°
C to 85
°
C (–40
°
F to 185
°
F)
Operation (Enclosed)
(Open Enclosure)
–20
°
C to 40
°
C (–4
°
F to 104
°
F)
–20
°
C to 55
°
C (–4
°
F to 131
°
F)
Maximum Altitude
2,000 M (6,562 ft.)
Relative Humidity
5% to 95% (non-condensing)
Cooling Method
Natural Convection
Vibration
1G Operational, 2.5G Non-operational
Shock
15 Operational, 30G Non-operational
Pollution Environment
Degree 2
ENVIRONMENTAL (Cont.)
Terminal Marking
CENELEC EN 50012
Finger Protection
(w/ contactor terminal cover)
(w/o contactor terminal cover)
(CT mounted and NEMA overload)
IP1X (Bul. 193-C1_1, 2, 3)
IP1X (Bul. 193-C1_4, 5)
IP0 (Bul. 193-C1_4, 5)
IP0 (Bul. 592 and Bul. 193-C1_6)
Electrostatic Discharge
8kV Air Discharge
RFI Susceptibility
10V/m
Fast Transient Susceptibility
2kV (AC Lines), 1kV
(Communication Lines)
Impulse Voltage Susceptibility
1kV (Line to line)
2kV (Line to ground)
Radiated Emissions
CISPR11 Group 1 Class A
Conducted Emissions
CISPR11 Group 1 Class A
PROTECTION FEATURES
Overload
Embedded Feature
Trip Class
Selectable (Class 10, 15, 20, or 30)
FLA Setting
Selectable (Up to a 5:1 range)
Phase Loss
Embedded Feature
Ground Fault
Selectable Feature
Jam/Stall
Selectable Feature