Chapter 6 – Serial Communication

6-4

Table 6.C SMP-3 Status Data

Bit

tat

ett

xp a at

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Status

Setting

Explanation

X

Out A

0
1

off
on

X

Out B

0
1

off
on

X

Control Status

0
1

Control Disabled
Control Enabled

X

Connection
Indication

X

Fixed (Help detect if connected)

X

Not Used

X

XXX

X

X

X

Analog Feedback
Designator

000
001
010
011
100

Default (Average Current)
Average Current
Thermal Capacity Utilized
Full Load Current Setting
Current Unbalance

X

X

X

X

X

X

X

X

Fault Code

0000

0000

0000

0001

0000

0010

0000

0011

0000

0100

0000

0101

0000

0110

0000

0111

0000

1000

No Fault
Trip/Test
Overload Fault
Phase Loss Fault
Ground Fault
Jam/Stall Fault
Illegal FLC Set Fault
Non-Vol Memory Fault
Comm Loss Fault

Note: The next 16 bit word following the 16 bit Status Data
word is the unscaled analog value of the parameter selected by
bits 13–15 in the Logic Control Data word.