Operation 17 – Rockwell Automation 836E Solid-State Pressure Sensors User Manual

Page 17

background image

Operation

17

4 - 20

Analog output

Value for 4 mA
(LRV)

Enter lower range
value in increments
of 0.1%

Value for 20 mA
(URV)

Enter upper range
value in increments
of 0.1%

Pressure applied for
4 mA (LRV)

Use measured
pressure as lower
range value

Pressure applied for
20 mA (URV)

Use measured
pressure as upper
range value

Error current

Current value in
event of error:
MIN = ≤ 3.6 mA
MAX = ≥ 21.0 mA
HOLD = last value

Range of adjustment: LRL = Lower Range Limit; URL = Upper Range Limit;
LRV = Lower Range Value; URV = Upper Range Value

Turndown up to 4:1, LRV must be lower than URV