Operation
12
4.1.1
Navigating Through the Programming Menu
Refer to the menu structure in Figure 4.1.2 on the following page.
The section labeled A refers to Function groups
The section labeled B refers to the individual Functions within each Function group
The section labeled C identifies the possible values for each function
➀
To enter the operating menu:
• Press and hold the E key for longer than 3 sec.
➁
Once in programming mode (BASE will be displayed), toggle between the Function groups
with the + and − keys
➂
To enter the Function group, press the E key
➃
To toggle between functions, repeatedly press the E key (Note that repeatedly pressing the E
key will return you to the Function group.
• Then press the E key to return to the “Function” option
➄
Once on the desired function, use the + or − key to change the function value
➅
Press E to accept the function value
➆
To save changes, press and hold the E key for longer than 3 sec.
• Once in SAVE, choose YES or NO with the + or − key
• Confirm with the E key (sensor will go through a start-up routine before entering
operating mode)
• Warning code 210 (W210) will appear on the display to indicate a change in
configuration (see Chapter 6, ‘Troubleshooting’ for further explanations of Error and
Warning codes).
ATTENTION: Changes take effect only when you choose
YES when asked to save the data.