A-17 – Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual
Page 59
Specifications
A-17
PowerFlex SCR Bus Supply User Manual
Table A.F 600A Unit Spare Part Numbers/Descriptions
Item Availability
(1)
Description
Rockwell Catalog No.
Qty.
2
—
600A SCR Set
SK-20S-MCC312-18IO1
3
4
Yes
Fan Assembly
(2)
SK-D9-FAN2
1
6
—
400A and 600A MOV Assembly
SK-20S-VBKSDK041
1
7
Yes
40A Fuse (Precharge fuses F6…F8)
(3)
SK-20S-F070B040S or
Westcode Type F070B040S or
Ferraz Shawmut Type 6.921CPgRC14.51 40
3
10
Yes
630A, 700V Fuse (AC fuses F1…F3)
Torque to 25 N•m (221 lb•in).
SK-20S-069UR5S0630B or
Westcode Type 069UR2S0630B or
Ferraz Shawmut Type 6.9URD32TTF0630
3
11
Yes
1000A, 700V Fuse (DC fuses F4 and F5)
Torque to 25 N•m (221 lb•in).
SK-20S-069UR2S1000B or
Westcode Type 069UR2S1000B or
Ferraz Shawmut Type 6.9URD32TTF1000
2
12
Yes
Fuse Monitoring Switch
SK-20S-MS3V1-5
5
13
—
85 °C Thermostat
SK-20S-SWT85KSDKRW
1
15
—
600A SCR Wire Harness
SK-20S-ZY065-600
1
18
Yes
400 and 600A Snubber Circuit Board
SK-20S-PR-GR3
1
19
—
600A and 1000A Cover
SK-20S-RW9582300-A
1
22
—
600A and 1000A Enclosure
SK-20S-RWU600-1000
1
24
—
10 µF, 1200V Capacitor
SK-20S-E62K85103D1W
2
25
—
5.6K Ohm, 90W Resistor
SK-20S-RW35FST5K6K
2
27
—
4.7 Ohm, 45W Resistor
SK-20S-RW33FST4R7K
1
29
—
600A Bus Bar Set
SK-20S-BBKSDK065
1
31
—
Terminal Block Assembly
SK-20S-TBKSDKRW
1
32
—
40 mm tall x 40 mm O.D. Insulator
with M10 Thread
SK-20S-IN551520
5
35
Yes
480V SCR Precharge Circuit Board
(4)
SK-D9-SCRPRE1-D
1
38
Yes
Precharge Relay
SK-20S-CA2KN31F7
1
(1)
Important: SCR Bus Supplies are designed to be field maintained only. Normal maintenance components (fan, fuses, fuse
monitor switch, printed circuit boards (precharge, gate, and snubber), and precharge relay are available. Additional catalog
numbers are provided for troubleshooting and technical support information only.
(2)
Extensive disassembly is required to replace the fan assembly. Please consider using Rockwell Automation Remanufacturing
Services.
(3)
When replacing these fuses, always properly position them so that their fuse trip indicators (plungers) point toward the fuse trip
detection board.
(4)
This is an ESD sensitive component.