Accessories, Line reactors – Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual
Page 49
Specifications
A-7
PowerFlex SCR Bus Supply User Manual
Accessories
Line Reactors
A minimum reactance is required to limit peak currents in the AC line and
the bridge circuit. This can be accomplished either by a matched supply
transformer or by adding line reactors to ensure the requested minimum
voltage drop over the total line impedance. The preferred method is to
install a minimum 3% line reactor, which will also reduce line harmonics.
Use
Table A.A
to select a line reactor based on the sum
of the drive’s connected DC Amps and the supply transformer rating.
For more details on the 1321-Series line reactors, see the 1321 Power
Conditioning Products Technical Data (publication 1321-TD001).
Table A.A 400V, 50Hz Line Reactor Selection
Drives
Ranges of Drives DC Amp Sum for Typical Supply Transformers
(1)
Line Reactor
Sum of
DC Amps
630 kVA
5%
43
µ
H
800 kVA
5%
35
µ
H
1000 kVA
5.5%
31
µ
H
1250 kVA
6%
27
µ
H
1600 kVA
6%
22
µ
H
2500 kVA
6.5%
16
µ
H
3000 kVA
6.5%
13
µ
H
Induct.
[
µ
H]
Catalog No.
1321-
…
(2)
up to 203
120-150
120-154
120-160
120-165
120-168
120-173
120-176
230
3R160-C
151-203
155-203
161-203
166-203
169-203
174-203
177-203
150
3R160-B
75
3R160-A
204 to 255
—
—
—
204-206
204-209
204-219
204-224
185
3R200-C
204-255
204-255
204-255
207-255
210-255
220-255
225-255
110
3R200-B
55
3R200-A
256 to 319
—
—
—
—
—
256-260
256-275
150
3RB250-C
256-319
256-319
256-319
256-319
256-319
261-319
276-319
90
3RB250-B
45
3RB250-A
320 to 407
125
3RB320-C
320-335
320-370
320-390
320-407
320-407
320-407
320-407
75
3RB320-B
336-407
371-407
391-407
—
—
—
—
40
3RB320-A
408 to 509
105
3RB400-C
—
408-425
408-450
408-480
408-509
408-509
408-509
60
3RB400-B
408-509
426-509
451-509
481-509
—
—
—
30
3RB400-A
510 to 635
—
—
—
510-538
510-590
510-635
510-635
50
3R500-B
510-540
510-580
510-635
539-635
591-635
—
—
25
3R500-A
636 to 763
—
—
—
—
636-660
636-763
636-763
40
3R600-B
—
636-763
636-763
636-763
661-763
—
—
20
3R600-A
764 to 938
—
—
—
—
—
764-900
764-938
29
3R750-B
—
764-800
764-870
764-900
764-938
901-938
—
15
3R750-A
939 to 1K0
—
—
—
—
—
939-1K0
939-1K0
27
3R850-B
—
—
—
—
939-1K0
—
—
15
3R850-A
(1)
The inductance value of the supply transformers includes 2.5 µH for 10 m feeder cable.
(2)
The number in the catalog string represents the fundamental AC current rating of the reactor.