Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual
Page 50
A-8
Specifications
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Table A.B 480V, 60Hz Line Reactor Selection
Drives
Ranges of Drives DC Amp Sum for Typical Supply Transformers
(1)
Line Reactor
Sum of
DC Amps
630 kVA
5%
51
µ
H
800 kVA
5%
41
µ
H
1000 kVA
5.5%
36
µ
H
1250 kVA
6%
32
µ
H
1600 kVA
6%
26
µ
H
2500 kVA
6.5%
19
µ
H
3000 kVA
6.5%
16
µ
H
Induct.
[
µ
H]
Catalog No.
1321-
…
(2)
up to 203
120-140
120-144
120-150
120-155
120-160
120-165
120-170
230
3R160-C
141-203
145-203
151-203
156-203
161-203
166-203
171-203
150
3R160-B
204 to 255
—
—
—
—
204-209
204-214
204-218
185
3R200-C
204-255
204-255
204-255
204-255
210-255
215-255
219-255
110
3R200-B
55
3R200-A
256 to 319
—
—
—
—
—
—
256-260
150
3RB250-C
256-290
256-319
256-319
256-319
256-319
256-319
261-319
90
3RB250-B
291-319
—
—
—
—
—
—
45
3RB250-A
320 to 407
—
320-340
320-360
320-380
320-407
320-407
320-407
75
3RB320-B
320-407
341-407
361-407
381-407
—
—
—
40
3RB320-A
408 to 509
—
—
408-420
408-450
408-490
408-509
408-509
60
3RB400-B
408-440
408-509
421-509
451-509
491-509
—
—
30
3RB400-A
510 to 635
—
—
—
—
510-540
510-620
510-635
50
3R500-B
510-560
510-585
510-600
510-635
541-635
621-635
—
25
3R500-A
636 to 763
—
—
—
—
—
636-700
636-763
40
3R600-B
—
636-680
636-763
636-763
636-763
701-763
—
20
3R600-A
764 to 938
—
—
—
—
—
764-840
764-938
29
3R750-B
—
—
—
764-938
764-938
841-938
—
15
3R750-A
939 to 1K0
—
—
—
—
—
939-1K0
939-1K0
27
3R850-B
—
—
—
—
939-1K0
—
—
15
3R850-A
(1)
The inductance value of the supply transformers includes 2.5 µH for 10 m feeder cable.
(2)
The number in the catalog string represents the fundamental AC current rating of the reactor.