Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual

Page 50

background image

A-8

Specifications

PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P

Table A.B 480V, 60Hz Line Reactor Selection

Drives

Ranges of Drives DC Amp Sum for Typical Supply Transformers

(1)

Line Reactor

Sum of
DC Amps

630 kVA
5%
51

µ

H

800 kVA
5%
41

µ

H

1000 kVA
5.5%
36

µ

H

1250 kVA
6%
32

µ

H

1600 kVA
6%
26

µ

H

2500 kVA
6.5%
19

µ

H

3000 kVA
6.5%
16

µ

H

Induct.
[

µ

H]

Catalog No.
1321-

(2)

up to 203

120-140

120-144

120-150

120-155

120-160

120-165

120-170

230

3R160-C

141-203

145-203

151-203

156-203

161-203

166-203

171-203

150

3R160-B

204 to 255

204-209

204-214

204-218

185

3R200-C

204-255

204-255

204-255

204-255

210-255

215-255

219-255

110

3R200-B

55

3R200-A

256 to 319

256-260

150

3RB250-C

256-290

256-319

256-319

256-319

256-319

256-319

261-319

90

3RB250-B

291-319

45

3RB250-A

320 to 407

320-340

320-360

320-380

320-407

320-407

320-407

75

3RB320-B

320-407

341-407

361-407

381-407

40

3RB320-A

408 to 509

408-420

408-450

408-490

408-509

408-509

60

3RB400-B

408-440

408-509

421-509

451-509

491-509

30

3RB400-A

510 to 635

510-540

510-620

510-635

50

3R500-B

510-560

510-585

510-600

510-635

541-635

621-635

25

3R500-A

636 to 763

636-700

636-763

40

3R600-B

636-680

636-763

636-763

636-763

701-763

20

3R600-A

764 to 938

764-840

764-938

29

3R750-B

764-938

764-938

841-938

15

3R750-A

939 to 1K0

939-1K0

939-1K0

27

3R850-B

939-1K0

15

3R850-A

(1)

The inductance value of the supply transformers includes 2.5 µH for 10 m feeder cable.

(2)

The number in the catalog string represents the fundamental AC current rating of the reactor.