Essential requirements for ce compliance – Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual
Page 34
1-20
Installation/Wiring
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
• Conformity of the drive with CE EMC requirements does not guarantee
an entire machine installation complies with CE EMC requirements.
Many factors can influence total machine/installation compliance.
Essential Requirements for CE Compliance
Conditions 1…5 listed below must be satisfied for the PowerFlex SCR Bus
Supply to meet the requirements of EN61800-3.
1. Bus Supply and inverter must be PowerFlex type and CE compatible.
2. Externally mounted Line Reactor and HF filter (specified in
) must be connected to the line input as shown in
Figure 1.8 on page 1-12
.
3. Review important precaution/attention statements throughout this
document before installing the drive(s).
General Grounding Requirements on
.
5. Control wiring and DC bus wiring leaving the cabinet must be braided,
shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.
For additional conditions, refer to the respective drive Reference Manual.