A-10, Table a.d – Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual
Page 52

A-10
Specifications
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Table A.D 690V, 50Hz Line Reactor Selection
Drives
Ranges of Drives DC Amp Sum for Typical Supply Transformers
(1)
Line Reactor
Sum of
DC Amps
630 kVA
5%
123
µ
H
800 kVA
5%
95
µ
H
1000 kVA
5.5%
86
µ
H
1250 kVA
6%
75
µ
H
1600 kVA
6%
59
µ
H
2500 kVA
6.5%
42
µ
H
3000 kVA
6.5%
33
µ
H
Induct.
[
µ
H]
Catalog No.
1321-
…
(2)
up to 203
—
130-150
130-157
130-162
130-170
140-180
150-185
2x150 3R160-B
(3)
130-175
151-190
158-203
163-203
171--203
181-203
186-203
230
3R160-C
176-203
191-203
—
—
—
—
—
150
3R160-B
75
3R160-A
204 to 255
—
—
—
—
—
204-210
204-220
2x110 3R200-B
(3)
204-206
204-230
204-245
204-255
204-255
211-255
221-255
185
3R200-C
207-255
231-255
246-255
—
—
—
—
110
3R200-B
55
3R200-A
256 to 319
—
—
—
—
—
—
256-260
2x90
3RB250-B
(3)
—
256-260
256-270
256-290
256-319
256-319
261-319
150
3RB250-C
256-280
261-319
271-319
291-319
—
—
—
90
3RB250-B
281-319
—
—
—
—
—
—
45
3RB250-A
320 to 407
—
—
—
—
320-360
320-407
320-407
125
3RB320-C
—
320-360
320-380
320-407
361-407
—
—
75
3RB320-B
320-407
361-407
381-407
—
—
—
—
40
3RB320-A
408 to 509
—
—
—
—
—
408-465
408-509
105
3RB400-C
—
—
408-414
408-450
408-509
466-509
—
60
3RB400-B
—
408-500
415-509
451-509
—
—
—
30
3RB400-A
510 to 635
—
—
—
—
—
510-520
510-580
85
3R500-C
—
—
—
510-538
510-570
521-635
581-635
50
3R500-B
—
—
510-540
539-635
571-635
—
—
25
3R500-A
636 to 763
—
—
—
—
—
—
636-650
65
3R600-C
—
—
—
—
—
636-763
651-763
40
3R600-B
—
—
—
—
661-763
—
—
20
3R600-A
764 to 938
—
—
—
—
—
—
764-780
48
3R750-C
—
—
—
—
—
764-850
781-938
29
3R750-B
—
—
—
—
—
851-938
—
15
3R750-A
939 to 1K0
—
—
—
—
—
—
—
42
3R850-C
—
—
—
—
—
939-1K0
939-1K0
27
3R850-B
—
—
—
—
—
—
—
15
3R850-A
(1)
The inductance value of the supply transformers includes 2.5 µH for 10 m feeder cable.
(2)
The number in the catalog string represents the fundamental AC current of the reactor.
(3)
Connect two reactors in series.