PowerFlex SCR Bus Supply
Specifications Dependent on Power and Voltage
The derate for each additional slave is 5% plus 5% for the master. See
Parallel Connection of Slave Units on page 1-15
.
Specifications Dependent on Voltage
Topic
Page
Category Specification
SCR Bus Supply Catalog Number
20SD400
…
20SD600
…
20SD1K0
…
20SF1K0
…
Input
Ratings
Nominal AC Input Voltage:
400/480V
600/690V
Frequency:
47…63 Hz
47…63 Hz
Operational AC Input Voltage Range:
187…528V
528…759V
Input Current (Max. Continuous rms):
355
521
843
843
Input kVA at Max. Continuous rms Amps:
246/295
361/433
584/700
876/1007
Output
Ratings
DC Bus Amps
Normal Duty/Heavy Duty
Continuous:
1 minute:
3 Sec. every minute:
300/240
330/360
450/480
500/400
550/600
750/800
800/720
880/1080
1200/1440
800/720
880/1080
1200/1440
Max. Continuous DC Bus Amps
without Overload:
400
600
1000
1000
Power Dissipation
(1)
— Watts at
Maximum Continuous Amps:
1200
1600
2700
2800
(1)
Includes appropriate AC line reactor.
AC Input
Voltage
DC Bus Voltage
Nominal
Maximum
400V
540V
750V
480V
650V
750V
600V
810V
1080V
690V
930V
1080V