Rockwell Automation 20G PowerFlex SCR Bus Supply User Manual
Page 51
Specifications
A-9
PowerFlex SCR Bus Supply User Manual
Table A.C 600V, 60Hz Line Reactor Selection
Drives
Ranges of Drives DC Amp Sum for Typical Supply Transformers
(1)
Line Reactor
Sum of
DC Amps
630 kVA
5%
78
µ
H
800 kVA
5%
62
µ
H
1000 kVA
5.5%
55
µ
H
1250 kVA
6%
48
µ
H
1600 kVA
6%
38
µ
H
2500 kVA
6.5%
27
µ
H
3000 kVA
6.5%
21
µ
H
Induct.
[
µ
H]
Catalog No.
1321-
…
(2)
up to 203
120-155
120-164
120-175
130-180
130-190
130-199
140-203
230
3R160-C
156-203
165-203
176-203
181-203
191-203
200-203
—
150
3R160-B
75
3R160-A
204 to 255
—
—
204-209
204-230
204-230
204-255
204-255
185
3R200-C
204-255
204-255
210-255
231-255
231-255
—
—
110
3R200-B
55
3R200-A
256 to 319
—
—
—
—
256-270
256-295
256-319
150
3RB250-C
256-280
256-319
256-319
256-319
271-319
296-319
—
90
3RB250-B
281-319
—
—
—
—
—
—
45
3RB250-A
320 to 407
—
320-340
320-360
320-390
320-407
320-407
320-407
75
3RB320-B
320-407
341-407
361-407
391-407
—
—
—
40
3RB320-A
408 to 509
—
—
—
—
—
—
408-425
105
3RB400-C
—
—
—
408-440
408-509
408-509
426-509
60
3RB400-B
408-450
408-509
408-509
441-509
—
—
—
30
3RB400-A
510 to 635
—
—
—
—
510-545
510-635
510-635
50
3R500-B
—
510-560
510-600
510-635
546-635
—
—
25
3R500-A
636 to 763
—
—
—
—
—
636-740
636-763
40
3R600-B
—
—
—
636-750
636-763
741-763
—
20
3R600-A
764 to 938
—
—
—
—
—
764-840
764-938
29
3R750-B
—
—
—
—
764-938
841-938
—
15
3R750-A
939 to 1K0
—
—
—
—
—
939-1K0
939-1K0
27
3R850-B
—
—
—
—
939-1K0
—
—
15
3R850-A
(1)
The inductance value of the supply transformer includes 2.5 µH for 10 m feeder cable.
(2)
The number in the catalog string represents the fundamental AC current rating of the reactor.