Adapter Parameters
B-3
06
[Baud Rate Cfg]
Sets the baud rate (kilobits per second) at which
the adapter communicates. (Updates Parameter
07 - [Baud Rate Act] after a reset.)
Default:
0 = Autobaud
Values:
0 = Autobaud
1 = 9600 kbps
2 = 19200 kbps
3 = 38400 kbps
4 = 76800 kbps
Type:
Read/Write
Reset Required:
Yes
07
[Baud Rate Act]
Displays the baud rate (kilobits per second)
actually used by the adapter.
Default:
0 = Unknown
Values:
0 = Unknown
1 = 9600 kbps
2 = 19200 kbps
3 = 38400 kbps
4 = 76800 kbps
Type:
Read Only
08
[MAC Address]
Displays the address set by the MAC Address
Switches SW1…SW7 (
) on the adapter.
This value is latched when the adapter powers up.
Default:
0
Minimum:
0
Maximum:
127
Type:
Read Only
09
[Max Master]
Sets the maximum MAC Address for any device in
the BACnet MS/TP token ring.
Default:
127
Minimum:
0
Maximum:
127
Type:
Read/Write
Reset Required:
Yes
10
[Max Info Frames]
Sets the maximum number of messages that the
adapter can transmit while it owns the token.
Default:
1
Minimum:
1
Maximum:
255
Type:
Read/Write
Reset Required:
Yes
11
[Device Inst Hi]
Sets the high portion (most significant digits) of
the Device Instance Number. The Device Instance
Number used by the adapter is the value of this
parameter times 1000 plus the value of Parameter
12 - [Device Inst Lo].
Default:
160
Minimum:
0
Maximum:
4194
Type:
Read/Write
Reset Required:
Yes
12
[Device Inst Lo]
Sets the low portion (always the last three least
significant digits) of the Device Instance Number.
The Device Instance Number used by the adapter
is the value of Parameter 11 - [Device Inst Hi]
times 1000 plus the value of this parameter.
Default:
0
Minimum:
0
Maximum:
999
Type:
Read/Write
Reset Required:
Yes
Parameter
No. Name and Description
Details