beautypg.com

Rockwell Automation 22-COMM-B PowerFlex BACnet MS/TP Adapter User Manual

Page 50

background image

5-6

Troubleshooting

7–9

Reserved

DSI Events

10

Slave Detected

The adapter detected that the slave has been connected.

11

Slave Removed The adapter detected that the slave has been disconnected.

12

Slave Logon

The adapter has established communications with the slave.

13

Slave Timeout

The adapter has lost communications with the slave.

14

Slave Brand Flt

The slave brand is different than the adapter.

15

Host 0 Logon

The adapter has established communications with the drive.

16-19 Reserved

20

Host 0 Timeout

The adapter has lost communications with the drive.

21-24 Reserved

25

Host 0 Brand Flt The drive is not an Allen-Bradley brand drive.

26–39 Reserved

Network Events

40

Net Link Up

The network link is established.

41

Net Link Down

The network link is lost.

42

Dup Net Addr

The adapter detected that another device is using its network
address. In this case, the adapter will not participate in any
network activity.

43

Net Open

An I/O connection from the network to the adapter was opened.

44

Net Close

An I/O connection from the network to the adapter was closed.

45

Net Timeout

An I/O connection from the network to the adapter has timed
out.

46

Net Comm Flt

The adapter has performed the “Comm Flt” action specified by
the user.

47

Net Idle Flt

The adapter has performed the “Idle Flt” action specified by the
user.

48

PCCC IO Open

The adapter has begun receiving PCCC Control messages (the
PCCC Control Timeout was previously set to a non-zero value).

49

PCCC IO Close The device sending PCCC Control messages to the adapter

has set the PCCC Control Timeout to a value of zero.

50

PCCC IO Time
Flt

The adapter has not received a PCCC Control message for
longer than the PCCC Control Timeout.

51

Net Sent Reset

The adapter received a reset from the network.

52

Msg Ctrl Open

The adapter has begun receiving Client-Server Control
messages (the Client-Server Control Timeout was previously
set to a non-zero value).

53

Msg Ctrl Close

The device sending Client-Server Control messages to the
adapter has set the Client-Server Control Timeout to a value of
zero.

54

Msg Ctrl
Timeout

The adapter has not received a Client-Server Control message
for longer than the established timeout period.

Code Event

Description