Verifying/setting key adapter parameters, Configuring/verifying key drive parameters – Rockwell Automation 22-COMM-B PowerFlex BACnet MS/TP Adapter User Manual
Page 26
2-10
Installing the Adapter
Table 2.B Drive and Adapter Start-Up Status Indications
Verifying/Setting Key Adapter Parameters
For instructions to use an optional PowerFlex 4-Class HIM to access
adapter parameters, see
Using the Optional, External PowerFlex 4-Class
.
1. Verify that adapter Parameter 08 - [MAC Address] is reporting the
MAC address set in
Setting the MAC Address on page 2-2
2. Set adapter Parameters 11 - [Device Inst Hi] and 12 - [Device Inst
Lo] to establish a unique number for representation to the Building
Automation Controller. For more information, see
.
3. Reset the adapter by setting adapter Parameter 01 - [Reset Module]
to “1” (Reset Module) to apply the new Device Instance Number.
Configuring/Verifying Key Drive Parameters
The PowerFlex 4-Class drive can be separately configured for the control
and reference functions in various combinations. For example, you
could set the drive to have its control come from a peripheral or terminal
block with the reference coming from the BACnet MS/TP network. Or
you could set the drive to have its control come from the BACnet MS/TP
network with the reference coming from another peripheral or terminal
block. Or you could set the drive to have both its control and reference
come from the BACnet MS/TP network.
Item Name
Color
State
Description
Drive FAULT Status Indicator
➊
FAULT
Red
Off
Drive ready but not running, and no faults are present.
Flashing
A fault has occurred.
Adapter Status Indicators
➋
PORT
Green
Flashing
Normal Operation. The adapter is establishing
communications with the drive. It will turn solid green or red.
Steady
Normal Operation. The adapter is properly connected and
communicating with the drive
MOD
Green
Flashing
Normal Operation. The adapter is operating but is not
transferring I/O data.
Steady
Normal Operation. The adapter is operating and transmitting
I/O data.
NET A
Green
Flashing
Normal Operation. The adapter is properly connected and
communicating on the network.
NET B
Green
Off
Normal Operation. The adapter is properly connected but is
idle.
Flashing