Appendix b, Adapter parameters, About parameter numbers – Rockwell Automation 22-COMM-B PowerFlex BACnet MS/TP Adapter User Manual
Page 53: Parameter list, Badapter parameters

Appendix
B
Adapter Parameters
Appendix B provides information about the adapter parameters.
The parameters in the adapter are numbered consecutively. However,
depending on which configuration tool you use, they may have different
numbers.
Topic
Page
About Parameter Numbers
Configuration Tool
Numbering Scheme
•
DriveExplorer
•
DriveExecutive
•
HIM
The adapter parameters begin with parameter 1. For
example, Parameter 01 - [Reset Module] is parameter 1 as
indicated by this manual.
Parameter List
Parameter
No. Name and Description
Details
01
[Reset Module]
No action if set to “0” (Ready). Resets the adapter
if set to “1” (Reset Module). Restores the adapter
to its factory default settings if set to “2” (Set
Defaults). This parameter is a command. It will be
reset to “0” (Ready) after the command has been
performed.
Default:
0 = Ready
Values
0 = Ready
1 = Reset Module
2 = Set Defaults
Type:
Read/Write
Reset Required:
No
!
ATTENTION: Risk of injury or equipment damage exists. If the adapter is
transmitting I/O that controls the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting a connected
adapter.