Frame 3a drives, Frame 3b drives, Frame 3a drives -30 frame 3b drives -30 – Rockwell Automation 20L PowerFlex 700L Liquid-Cooled Adjustable Frequency AC Drive User Manual
Page 78
3-30
Frame 3A and 3B Installation
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P
2. Connect the three-phase AC power motor leads to the U/T1, V/T2, and
W/T3 output power terminals on the drive:
– Frame 3A Combined Converter/Inverter Power Module (for terminal
locations, see
and
).
– Frame 3A Dual Inverter Power Module (for terminal locations, see
– Frame 3B Separate Converter Power Module (for terminal locations,
see
).
3. Tighten the AC output power terminal connections to the proper torque
as shown in
Installing Control Wiring
from the Input Filter Bay to
the Power Module Bay
This section provides details on control wiring between the Input Filter Bay
and the Power Module Bay. When a Frame 3A or 3B Complete Drive is
ordered, wiring from the Input Filter Bay to the Power Module Bay is
completed at the factory. In this case, this section can be used as verification
or reference for installation or maintenance.
Frame 3A Drives
Connect wiring to terminals in accordance with
Table 3.D
,
Table 3.A
,
Table 3.E
,
Figure 3.29
, and the Frame 3A drive schematic on
Frame 3B Drives
Connect wiring to terminals in accordance with
Table 3.D
,
Table 3.A
,
Table 3.E
,
Figure 3.30
, and the Frame 3B drive schematic on
or
!
ATTENTION: Risk of equipment damage exists. Do not use
power module terminal blocks TB5-1 and TB5-3 to connect any
type of power wiring for auxiliary equipment. These terminals are
for only low amperage control wiring.
!
ATTENTION: Do not route signal and control wiring with
power wiring in the same conduit. This can cause interference
with drive operation. Failure to observe this precaution can result
in damage to, or destruction of, the equipment.