700s phase ii control fault descriptions, Clearing alarms – Rockwell Automation 20L PowerFlex 700L Liquid-Cooled Adjustable Frequency AC Drive User Manual
Page 114
6-6
Troubleshooting
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P
700S Phase II Control Fault
Descriptions
Table 6.C 700S Phase II Control Fault Types, Descriptions, and Actions
Clearing Alarms
Alarms are automatically cleared when the condition that caused the alarm
is no longer present.
Fault
No.
Type
(1)
Description
Action
700L Dsat Phs U1
F097
Phase U Dsat fault on 700L power structure.
Contact Technical Support.
700L Dsat Phs V1
F098
Phase V Dsat fault on 700L power structure.
Contact Technical Support.
700L Dsat Phs W1
F099
Phase W Dsat fault on 700L power structure.
Contact Technical Support.
700L Ovr Current1
F100
Over current on 700L power structure.
Check programming. Check for cause of excessive current.
700L Ovr Volt1
F101
Over voltage on 700L power structure.
Check programming. Check for cause of excessive voltage.
700L AsymDcLink1
F102
Asymmetrical voltage on the 700L power
structure dc link.
Verify load balance resistors.
700L Pwr Suply1
F103
Power supply failed on 700L power structure.
Replace power supply if problem persists.
700L HW Disable1
F104
Hardware disable asserted on 700L power
structure.
Verify drive enable is present.
700L Latch Err1
F105
Fault reporting failure on 700L power structure. Contact Technical Support.
700L Fan Fail1
F106
Fan failure on 700L power structure.
Verify internal circulating fans are turning.
700L Cnv Faulted
F110
Active converter has faulted.
Check active converter fault log.
Cnv NotLogin
F111
Active converter did not begin communication.
Check DPI connection. Check for proper versions.
Cnv NotStart
F112
Active converter did not start when requested.
Check start inhibits. Check parameter 214 - [Start Inhibits].
700L Dsat Phs U2
F113
Phase U Dsat fault on secondary 700L power
structure.
Contact Technical Support.
700L Dsat Phs V2
F114
Phase V Dsat fault on secondary 700L power
structure.
Contact Technical Support.
700L Dsat Phs W2
F115
Phase W Dsat fault on secondary 700L power
structure.
Contact Technical Support.
700L Ovr Current2
F116
Over current on secondary 700L power
structure.
Check programming. Check for cause of excessive current.
700L Ovr Volt2
F117
Over voltage on secondary 700L power
structure.
Check programming. Check for cause of excessive voltage.
700L AsymDcLink2
F118
Asymmetrical voltage on secondary 700L
power structure dc link.
Verify load balance resistors.
700L Pwr Suply2
F119
Power supply failed on secondary 700L power
structure.
Replace power supply if problem persists.
700L HW Disable2
F120
Hardware disable asserted on secondary 700L
power structure.
Verify drive enable is present.
700L Latch Err2
F121
Fault reporting failure on secondary 700L power
structure.
Contact Technical Support.
700L Fan Fail2
F122
Fan failure on secondary 700L power structure. Verify internal circulating fans are turning.