700S Phase II Control Fault
Descriptions

Table 6.C 700S Phase II Control Fault Types, Descriptions, and Actions

Clearing Alarms

Alarms are automatically cleared when the condition that caused the alarm
is no longer present.

Fault

No.

Type

(1)

Description

Action

700L Dsat Phs U1

F097

Phase U Dsat fault on 700L power structure.

Contact Technical Support.

700L Dsat Phs V1

F098

Phase V Dsat fault on 700L power structure.

Contact Technical Support.

700L Dsat Phs W1

F099

Phase W Dsat fault on 700L power structure.

Contact Technical Support.

700L Ovr Current1

F100

Over current on 700L power structure.

Check programming. Check for cause of excessive current.

700L Ovr Volt1

F101

Over voltage on 700L power structure.

Check programming. Check for cause of excessive voltage.

700L AsymDcLink1

F102

Asymmetrical voltage on the 700L power
structure dc link.

Verify load balance resistors.

700L Pwr Suply1

F103

Power supply failed on 700L power structure.

Replace power supply if problem persists.

700L HW Disable1

F104

Hardware disable asserted on 700L power
structure.

Verify drive enable is present.

700L Latch Err1

F105

Fault reporting failure on 700L power structure. Contact Technical Support.

700L Fan Fail1

F106

Fan failure on 700L power structure.

Verify internal circulating fans are turning.

700L Cnv Faulted

F110

Active converter has faulted.

Check active converter fault log.

Cnv NotLogin

F111

Active converter did not begin communication.

Check DPI connection. Check for proper versions.

Cnv NotStart

F112

Active converter did not start when requested.

Check start inhibits. Check parameter 214 - [Start Inhibits].

700L Dsat Phs U2

F113

Phase U Dsat fault on secondary 700L power
structure.

Contact Technical Support.

700L Dsat Phs V2

F114

Phase V Dsat fault on secondary 700L power
structure.

Contact Technical Support.

700L Dsat Phs W2

F115

Phase W Dsat fault on secondary 700L power
structure.

Contact Technical Support.

700L Ovr Current2

F116

Over current on secondary 700L power
structure.

Check programming. Check for cause of excessive current.

700L Ovr Volt2

F117

Over voltage on secondary 700L power
structure.

Check programming. Check for cause of excessive voltage.

700L AsymDcLink2

F118

Asymmetrical voltage on secondary 700L
power structure dc link.

Verify load balance resistors.

700L Pwr Suply2

F119

Power supply failed on secondary 700L power
structure.

Replace power supply if problem persists.

700L HW Disable2

F120

Hardware disable asserted on secondary 700L
power structure.

Verify drive enable is present.

700L Latch Err2

F121

Fault reporting failure on secondary 700L power
structure.

Contact Technical Support.

700L Fan Fail2

F122

Fan failure on secondary 700L power structure. Verify internal circulating fans are turning.

(1)

See

page 6-1

for a description of fault types.