Powerflex 700s input voltage range/tolerance, X 70, Rang – Rockwell Automation 1336T FORCE to PowerFlex 700S Phase II Drive Conversion Guide User Manual
Page 59: Toler, Ance
1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide
59
PowerFlex 700S Input Voltage Range/Tolerance
HP
@ Motor (Drive Output)
Actual Line Voltage (Drive Input)
Full Power Range
Drive Operating Range
Nominal Motor Voltage -10%
Nominal Motor Voltage
Derated Power Range
No Drive
Output
Drive Rated Voltage
Drive Rated Voltage +10%
5 HP
3.7 HP
HP
@ Motor (Drive Output)
Actual Line Voltage (Drive Input)
342V
460V
No Drive
Output
480V
528V
Example:
Calculate the maximum power of a 5 HP, 460V motor
connected to a 480V rated drive supplied with 342V
Actual Line Voltage input.
• Actual Line Voltage / Nominal Motor Voltage = 74.3%
• 74.3%
×
5 HP = 3.7 HP
• 74.3%
×
60 Hz = 44.6 Hz
At 342V Actual Line Voltage, the maximum power the 5
HP, 460V motor can produce is 3.7 HP at 44.6 Hz.
Drive Rating
Nominal Line
Voltage
Nominal Motor
Voltage
Drive Full Power
Range
Drive Operating
Range
200-240
200
200†
200-264
180-264
208
208
208-264
240
230
230-264
380-400
380
380†
380-528
342-528
400
400
400-528
480
460
460-528
500-600
(Frames 1-4 Only)
600
575†
575-660
432-660
500-690
(Frames 5 & 6
Only)
600
575†
575-660
475-759
690
690
690-759
475-759
Drive Full Power Range =
Nominal Motor Voltage to Drive Rated Voltage + 10%.
Rated current is available across the entire Drive Full Power Range
Drive Operating Range
=
Lowest† Nominal Motor Voltage - 10% to Drive Rated Voltage +
10%.
Drive Output is linearly derated when Actual Line Voltage is less
than the Nominal Motor Voltage