Cable Recommendations - Control
Table G Recommended Control Wire
Type
Wire Type(s)
Description
Insulation
Rating
Digital I/O
Un-shielded
Per US NEC or applicable national or local code
–
300V, 60
o
C
(140
o
F),
Minimum
Shielded
Multi-conductor shielded cable such as Belden
8770(or equiv.)
0.750 mm
2
(18AWG), 3 conductor,
shielded.
Standard Analog I/O
Belden 8760/9460(or equiv.)
0.750 mm
2
(18AWG), twisted pair,
100% shield with drain
(5)
.
(5)
If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always
recommended.
300V,
75-90
º
C
(167-194
º
F)
Remote Pot
Belden 8770(or equiv.)
0.750 mm
2
(18AWG), 3 cond., shielded
Encoder/Pulse I/O
Less 30.5 m (100 ft.)
Combined:
Belden 9730 (or equivalent)
(1)
(1)
Belden 9730 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9728 (or equivalent).
0.196 mm
2
(24AWG), individually
shielded.
Encoder/Pulse I/O
30.5 m (100 ft.) to 152.4 m
(500 ft.)
Signal:
Belden 9730/9728 (or equivalent)
(1)
0.196 mm
2
(24AWG), individually
shielded.
Power:
Belden 8790
(2)
(2)
Belden 8790 is 1 shielded pair.
0.750 mm
2
(18AWG)
Combined:
Belden 9892
(3)
(3)
Belden 9892 is 3 individually shielded pairs (3 channel), 0.33 mm
2
(22 AWG) plus 1 shielded pair 0.5 mm
2
(20 AWG) for power.
0.330 mm
2
or 0.500 mm
2 (3)
Encoder/Pulse I/O
152.4 m (500 ft.) to 259.1 m
(850 ft.)
Signal:
Belden 9730/9728 (or equivalent)
(1)
0.196 mm
2
(24AWG), individually
shielded.
Power: Belden
8790
(2)
0.750 mm
2
(18AWG)
Combined:
Belden 9773/9774 (or equivalent)
(4)
(4)
Belden 9773 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9774 (or equivalent).
0.750 mm
2
(18AWG), individually
shielded pair.
Stegmann Encoder
Stegmann 6-411682-xx cables with C12 FUR connections
Resolver
Paige 412081 (or equiv.) Twist, capacitance, inductance and resistance
specifications equal to or greater than cable specified
0.750 =mm
2
(18 AWG), twisted pair
300V, 80
o
C (176
o
F) minimum
SynchLink
Versalink V-System, Lucent Technologies, Specialty Fibers Technology
Division 1403-CF BLK
200/230 micron HCS (Hard Clad Silica)
650 nm (Red) Data Rate 5 Mbps
EMC Compliance