1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide
31
Control Terminals
PowerFlex 700S
Table D TB1 Terminals
Terminal Signal
Factory Default Description
Related Params
1
Analog Input 1 Comm. (Volt)
Bipolar, differential input, +/-10V, 0-20 mA, 13 bit + sign
20k Ohm impedance at Volt; 500 Ohm impedance at mA
(1)
(1)
The Analog inputs are not isolated. However, the analog inputs can be connected in series when using current mode. Note that at 20mA the voltage source
must be capable of providing 10V dc at the drive terminals for one drive - - 20V dc is required for two drives and 30V dc is required for three drives, etc.
2
Analog Input 1 (+/-)
800
3
Shield
NA
Analog Input Shield
4
Analog Input 2 Comm. (Volt)
Bipolar, differential input, +/-10V, 0-20 mA, 13 bit + sign
20k Ohm impedance at Volt; 500 Ohm impedance at mA
(1)
5
Analog Input 2 (+/-)
806
6
Analog Input 3 [NTC-]
Comm.
(Volt)
Differential input, 0-10V, 10 bit (for motor control mode FOC2, this
is the temperature adaptation input).
(1)
7
Analog Input 3 [NTC+]
812
8
Shield
NA
Analog Output Shield
9
Analog Output 1 (-)
(Volt)
Bipolar, differential output, +/-10V, 0-20 mA, 11 bit + sign
2k Ohm minimum load
832, 833
10
Analog Output 1 (+)
11
Analog Output 2 (-)
(Volt)
839, 840
12
Analog Output 2 (+)
13
+10V Reference
NA
Rating: 20 mA maximum load (Recommend 5k Ohm pot)
14
Reference Common
NA
15
-10V Reference
NA
16
Encoder A
NA
Normal current draw per channel: 20 mA
230 - 234
17
Encoder A (Not)
NA
18
Encoder B
NA
19
Encoder B (Not)
NA
20
Encoder Z
NA
21
Encoder Z (Not)
NA
22
Encoder Reference
(+)
NA
12 or 5V DC power supply for primary encoder interface
Rating: 300 mA maximum
23
Encoder Reference (-) NA
24
Encoder Shield
NA
Connection point for encoder shield