1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide
11
PowerFlex 700S Phase II AC Drive Support
Rockwell Automation is committed to maintaining and supporting Allen-Bradley drives and installations.
Included in this commitment is start-up support and consultation for drive applications.
ProtectionPlus Drive Start-Up
With ProtectionPlus Drive Start-Up Services from Rockwell Automation, users can leverage the extensive product and
industry experience of Rockwell Automation technicians to quickly commission drives and reduce the time between
integration and actual start-up.
ProtectionPlus Drive Start-Up Services verify drive installation to ensure proper electrical, mechanical and environmental
criteria are met. This includes verification of power and I/O wiring to the drive, custom drive configuration/tuning to meet
application specific requirements, and diagnosing/troubleshooting problems that occur during a standalone drive start-up.
ProtectionPlus can also extend an eligible product parts warranty and add a labor warranty. For more information about
ProtectionPlus Drive Services, contact your local Rockwell Automation sales office or authorized distributor, or visit:
http://support.rockwellautomation.com/SupportPrograms/.
SupportPlus
For consultation on high performance drive applications, the SupportPlus program is offered. SupportPlus uses expert
level Rockwell Automation system engineers to support the user's engineering team. SupportPlus engineers will work
with the end user to layout the appropriate architecture, configure drives, recommend programming techniques and
provide application assistance on the most effective ways to implement the control solution.
For more information, please call 262-512-8176 or refer to www.ab.com/support/abdrives.
Add EtherNet to
PLC-5®
•
Ethernet Side-card
•
20-COMM-R (in drive)
•
20-COMM-E (in box)
•
20-XCOMM-DC-BASE
•
Ext. 24V DC supply
•
DIN rail to support 20-
XCOMM-DC-BASE &
Ext. 24V DC supply
•
Ethernet cables
1) Positions the system for future use with high-
end communication networks
2) Faster data throughput
3) Additional network flexibility
4) Can now use DriveTools SP to go online with
the drive and connected peripheral(s)
1) Expensive
2) Requires more mounting space
3) Must install new wiring
4) Need to modify existing PLC-5 program
Datalink Gateway
•
Datalink module w/ DH+
upgrade
•
20-COMM-S (in box)
•
20-COMM-R (in drive)
•
20-XCOMM-DC-BASE
•
Ext. 24V DC supply
•
DIN rail to support 20-
XCOMM-DC-BASE &
Ext. 24V DC supply
1) Can use existing DH+ cabling for connection
to 20-COMM-S
1) Expensive
2) Requires more mounting space
3) Need to modify existing PLC-5 program
4) Slow data throughput (38.4Kbps max)
5) Need to rely on 3rd-Party (Datalink) to update firmware in
future
6) Still using old comm. technology
7) Need 3rd-Party (Datalink) to update firmware to support
PCCC messaging for DriveTools SP
8) Need a separate power source for Datalink gateway (range
is 9 to 24V DC only)
Option Type:
Hardware Required:
Benefits: