1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide
10
Typical 1336 FORCE Network Configuration
Recommended Network Configuration Migration with PowerFlex 700S Phase II Drive
1336T FORCE to PowerFlex 700S Network Migration Solutions
Option Type:
Hardware Required:
Benefits:
Trade-Offs:
ControlLogix
Gateway
•
ControlLogix Chassis
•
20-COMM-R (in drive)
•
20-COMM-E (in box)
•
1756-EN2T or -ENBT
•
1756-DHRIO Card
•
20-XCOMM-DC-BASE
•
Ext. 24V DC supply
•
DIN rail to support -
BASE & supply
1) Fastest data throughput
2) Positions the system for future use with high-
end communication networks
3) Can now use DriveTools SP to go online with
the drive and connected peripheral(s)
4) Additional network flexibility
1) Expensive
2) Requires more mounting space
3) Must install new wiring
4) Need to convert PLC-5 program to work with ControlLogix
5) Need to train personal on how to use the new hardware
PLC5
w/DH+ and
Remote I/O
Remote I/O
DH+
1336 FORCE
with Multi-Comm
Adapter
ControlLogix Controller
with DHRIO Card
and EN2T Module
PLC5
w/DH+ and
Remote I/O
Remote I/O
DH+
EtherNet
EtherNet
Remote Work Station
20-XCOMM-DC-BASE
w/internal 20-COMM-E
PowerFlex 700S
with internal
20-COMM-R
w/Remote I/O
PORT
MOD
NET A
NET B
ControlLogix Gateway Solution