A - specifications, Stand alone regulator, Electrical – Rockwell Automation 23P PowerFlex DC Stand Alone Regulator and Gate Amplifier User Manual
Page 71: Environmental, Power dissipation, Gate amplifier, Appendix a, Specifications, Stand alone regulator gate amplifier, Appendix
Rockwell Automation Publication 23P-UM001D-EN-P - July 2012
71
Appendix
A
Specifications
Stand Alone Regulator
Electrical
Field Bridge
Input Voltage
100VAC…460VAC, ±10%, 50/60 Hz
Control Supply
Input Current
115VAC/1AAC or 230VAC/0.5AAC
Environmental
Operating Temperature 0
° C to 50 ° C (32 ° F to 122 ° F)
Storage Temperature
-25
° C to 55° C (-13 ° F to 131 ° F)
Relative Humidity
5% to 95%, Non-condensing
Note: Contamination from oils, corrosive vapors and abrasive debris must be
kept out of the enclosure.
Power Dissipation
Gate Amplifier
Electrical
Control Input
120VAC ±10%, 1.9 A, 47-63 Hz
Replacement fuse
Littelfuse 312005, 5 A, 250VAC, 3AG Time Delay
or equivalent.
Environmental
Operating Temperature 0
° C to 50 ° C (32 ° F to 122 ° F)
Storage Temperature
-40
° C to 70 ° C (-40 ° F to 158 ° F)
Relative Humidity
5% to 95%, Non-condensing
Note: Contamination from oils, corrosive vapors and abrasive debris must be
kept out of the enclosure.
Catalog
Number
Power Bridge AC
Input
Field Ratings
Total Watts
Loss
[V
AC
]
Input [V
AC
] Input [A
AC
]
Output [A
DC
] [W]
23PMD4
(230 to) 500
(230 to) 460
40
40
303
23PMD7
(230 to) 500
(230 to) 460
70
70
357
23PMF4
(575 to) 690
(230 to) 460
40
40
374
23PMF7
(575 to) 690
(230 to) 460
70
70
428